Clearances
Notes:
• Clearance of 42 inch is required in
front of chiller to other electrically grounded
parts.
• Two units facing each other or other
live parts require a clearance of 48 inches.
• 36-inch clearance is recommended
above the chiller
• See Figure 9 and Figure 10, p. 18 for
recommended clearance requirements for
array installations.
Figure 9. Clearance — FWCD single chiller application (all condenser options)