EasyManua.ls Logo

Johnson Controls A25 Series - Operation; Models A25 AN and A25 CN Operation

Johnson Controls A25 Series
9 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A25 Series Warm Air Control with Manual Reset Product/Technical Bulletin 5
O
peration
Models A25AN and A25CN
Setpoint Adjustment: Adjust the A25 setpoint by
rotating the setpoint knob (Figure 7). The setpoint
is displayed in the setpoint window.
Test Procedure:
To test (trip) the A25: Raise the temperature
at the sensor above the setpoint or lower the
setpoint below the ambient temperature. The
control should lockout (trip).
To reset after test: Lower the temperature at
the sensor to 20F° (11C°) below the setpoint or
raise the setpoint to 20F° (11C°) above the
ambient temperature. Press the reset lever.
The A25 should reset (closing the circuit).
Reset Procedure: Verify that the temperature has
dropped to 20F° (11C°) below setpoint. Press the
reset lever to reset the A25 (closing the circuit).
Figure 7: Models A25AN and A25CN

Related product manuals