General Features
Each device has 8 jumper selectable measuring ranges. Each device is individually temperature
compensated.
The Differential Pressure Transmitter is delivered individually packed with standard accessories
(see accessories).
Dimensions
Figure 1: Dimensions in mm
Mounting Instructions
Figure 2: Installation
(a). ZEROING: press the button over 4 seconds
(b). LED: long blink.....Zeroing
(c). RESPONSE TIME CHANGE: press the button shortly
(d). LED 3 x short blink means 0,8s selected
(e). LED 2 x long blink means 4s selected
Figure 3: Electrical Connection
Accessories
Standard accessories:
2 fixing screws
2 plastic duct connectors
2 m tube 4 / 7 mm
Optional accessories:
Metallic duct connectors
Model 2500
-100...+100 Pa
0...100 Pa
0...250 Pa
0...500 Pa
0...1000 Pa
0...1500 Pa
0...2000 Pa
0...2500 Pa
0-10 V Output 0...10 V
4-20 mA Output 4...20 mA
24 V Supply 24 VAC or VDC
GND Ground
Model: DP2500-R8 ( -D -AZ )
- R8 for 8 measuring range
- D for display
- AZ for autozero element
long term stability typical 1 year
± 1 Pa with AZ,
± 8 Pa without AZ