JC-460-000 2 I56-3750-001
fIgure 3. typIcal notIfIcatIon applIance cIrcuIt confIguratIon, nfpa style y:
(+)
(+)
(+)
(+)
(+)
(+)
47K EOL
RESISTOR
ELR-47K
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70.
LISTED FOR FIRE PROTECTION
WITH BATTERY BACKUP.
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO
LISTED COMPATIBLE CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
CONTROL
MODULE
FROM PANEL
OR PREVIOUS
DEVICE
TO NEXT
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
(–) (–)
(–)
(–)
(–)
(–)
C0947-00
fIgure 4. typIcal fault tolerant notIfIcatIon applIance cIrcuIt confIguratIon, nfpa style Z:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
MODULE POLARITIES ARE
SHOWN IN ALARM
EOL RESISTOR
IS INTERNAL
AT TERMINALS
8 AND 9
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT
IN AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
CONTROL
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL
PANELS ONLY
FROM PANEL
OR PREVIOUS
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10
& 11. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER
NFPA 70. LISTED FOR
FIRE PROTECTION WITH
BATTERY BACKUP.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0948-00
JC-460-000 3 I56-3750-001
fIgure 5. typIcal WIrIng for speaker superVIsIon anD sWItchIng, nfpa style y:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS
SUPERVISED AND POWER LIMITED
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
CONTROL
MODULE
47K EOL
RESISTOR
ELR-47K
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION.
REFER TO THE RELAY CONTACT RATING TABLE FOR
MAXIMUM LOAD.
TO NEXT
DEVICE
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AA-30, AA100 OR
AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0949-00
fIgure 6. typIcal fault tolerant WIrIng for speaker superVIsIon anD sWItchIng, nfpa style Z:
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
WIRES MUST BE SUPERVISED PER NFPA
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
CONTROL
MODULE
SPEAKERS MUST BE LISTED FOR
FIRE PROTECTION. REFER TO THE
RELAY CONTACT RATING TABLE FOR
MAXIMUM LOAD.
47K EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
MODULE POLARITIES ARE SHOWN IN ALARM
TO NEXT CONTROL
MODULE LAST MODULE
MUST RETURN WIRES FOR
SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.
SEE NOTIFIER INSTALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
USE ONLY MODELS AA-30, AA100 OR
AA-120. AMPLIFIER MUST PROVIDE
WIRING SUPERVISION PER NFPA.
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
BYPASS CAPACITORS: 100µ
A2143-20 NONPOLARIZED
<10µA LEAKAGE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0950-00