Do you have a question about the Johnson Controls M300CJ and is the answer not in the manual?
Addressable Control Module for Notification Appliances or telephone circuit monitoring.
Addressable Relay Module for dry-contact output to auxiliary devices.
Protocol enhancing communication speed between analog intelligent devices in groups.
Face plate material, rotary switches for address entry, and circuit configurations.
Each module uses a unique address on the SLC loop and reports its type and status.
Details on operating voltage, current draw, and external supply parameters.
Information on temperature, humidity ranges, and physical dimensions.
Details on operating voltage and current draw for the relay module.
Information on temperature, humidity ranges, and physical dimensions.
Provides maximum voltage and current ratings for resistive and inductive loads.
Diagram for typical notification appliance circuit configuration.
Diagram for fault-tolerant notification appliance circuit configuration.
Diagram for typical speaker supervision and switching.
Diagram for fault-tolerant speaker supervision and switching.
Wiring diagram for the M300RJ relay module.
The Johnson Controls M300CJ Control Module and M300RJ Relay Module are intelligent addressable devices designed for use with Johnson Controls fire alarm control panels. These modules leverage FlashScan® communication protocol for enhanced speed and efficiency.
Function Description: The M300CJ Control Module provides a circuit for Notification Appliances (horns, strobes, speakers, etc.) or monitors a telephone circuit. Its addressability allows it to be activated manually or through panel programming on a select (zone or area of coverage) basis. When commanded by the control panel, the M300CJ disconnects supervision and connects the external power supply in the proper polarity across the load device. This disconnection provides a positive indication to the panel that the control relay has turned ON. The external power supply is always relay isolated from the communication loop, ensuring that a trouble condition on the external power supply does not interfere with the rest of the system.
Important Technical Specifications:
Usage Features:
Maintenance Features:
Function Description: The M300RJ Addressable Relay Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Its addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis. The M300RJ can be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, and to reset four-wire smoke detector power.
Important Technical Specifications:
Usage Features:
Maintenance Features:
These modules are designed for reliable performance in fire protection systems, offering advanced features for control and monitoring of various fire alarm components.