EasyManuals Logo

Johnson Controls Metasys NAE55 User Manual

Johnson Controls Metasys NAE55
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Engine Commissioning for Modbus Vendor Integration
Application Note (LIT-12013150) for additional information.)
1. For a Modbus RTU device that requires an RS-485
connection, terminate the 2-wire bus cable from
the Modbus device to one of the removable 4-
terminal blue plugs on the network engine, labeled
FC-A and FC-B (Figure 10).
Figure 10: FC Bus terminal block and wiring
connections for Modbus
Table 5: FC Bus terminal block wiring for
Modbus
Callou
t
Description
1 FC Bus terminal block
2 FC Bus terminal block plug
3 Terminating wires for Modbus (2-wire cable
shown)
2. For a Modbus RTU device that requires an RS232C
serial connection, use a cable to connect the
converter to either the RS232C A or RS232C B serial
port on the network engine. The maximum cable
length between devices connected though an
RS-232 line depends on the baud rate used. In
general, the cable should not exceed 15 meters for
9600 baud.
3. Wire from the RS-485 terminal on the converter to
the RS-485 port on the vendor device (Figure 11).
The RS-485 bus is a two-wire network.
a. Connect the converter's + A terminal to the
device's + (or A) terminal.
b. Connect the converter's - B terminal to the
device's - (or B) terminal.
Figure 11: Connection between converter and device
4. To add additional vendor devices, wire from one
device to the next in a daisy chain configuration.
The completed wiring should look similar to Figure
12.
Figure 12: Modbus RTU wiring detail overview
Connecting M-Bus devices
About this task:
The network engine connects to the M-Bus network
devices by using the M-Bus Level Converter. Two
components are needed: serial connection cable (INT-DX-
KAB01) and the M-Bus Level Converter. (After installation
and wiring are complete, refer to the Network Engine
Commissioning for M-Bus Vendor Integration Application
Note (LIT-12013149) for additional information.)
1. Connect the RS-232 cable from either RS232C
serial port on the network engine to the RS-232
connection on the M-Bus Level Converter using
cable INT-DX-KAB01 (Figure 13). Wire to terminals
GND, RxD, and TxD (Table 6).
2. Wire from the M- and M+ terminals on the level
converter to the meters using a free (star, ring,
or bus) topology, preferably bus. Specific cabling
can vary depending on the topology and site. See
Wiring considerations and guidelines for network
integrations.
NAE55 Installation Guide 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Metasys NAE55 and is the answer not in the manual?

Johnson Controls Metasys NAE55 Specifications

General IconGeneral
BrandJohnson Controls
ModelMetasys NAE55
CategoryNetwork Hardware
LanguageEnglish

Related product manuals