VAV Controller—Variable Air Volume (VAV) Controller 53
The following table shows the HVAC PRO for Windows hardware point
assignments and options for single duct configurations.
Table 17: Single Duct Point Assignments and Options
Point
Type
Point
Name
HVAC PRO for Windows
Configuration
Assignments and Defaults
HVAC PRO for Windows
Configuration Options
Analog
AI 1 Zone Temperature None
Inputs
Unused Rename
Warmer/Cooler Adjust Potentiometer
Cooling Setpoint Potentiometer
AI 3 Unused Heating Setpoint Potentiometer
Rename
AI 4 Actuator Feedback on Pressure
Dependent
None
CFM on Pressure Independent None
Unused Rename
AI 5 Proportional Series Fan CFM None
Exhaust Box CFM None
Unused Rename
AI 6 Unused Box Supply Temperature for
Standalone Warmup in Pressure
Dependent with Feedback and
Independent Path
Rename
Binary
Inputs
BI 1 Unused Rename
Occupied
BI 2 Unused Rename
Standby
BI 3 Unused Rename
Shutdown Box Open
BI 4 Unused Rename
Shutdown Box Closed
Momentary
BI
BI 5 Unused Temporary Occupancy Mode
Boost Mode
Continued on next page . . .
Hardware Point
Assignment
Table