VAV Controller—Variable Air Volume (VAV) Controller 7
Table 1: VAV Controller Model Features
Feature VAV100/101
(Discontinued)
VAV110/111 VAV140/141
Ambient
Temperature
Rating
32 to 122F
(0 to 50C)
32 to 122F
(0 to 50C)
32 to 122F
(0 to 50C)
Analog Inputs
6
RTD temperature
elements (1000 ohm
nickel, platinum, or
silicon)
2k ohm setpoint
potentiometers
0 to 10 VDC or
0 to 2 VDC
transmitters
6
RTD temperature
elements (1000 ohm
nickel, platinum, or
silicon)
2k ohm setpoint
potentiometers
0 to 10 VDC or
0 to 2 VDC
transmitters
6
RTD temperature
elements (1000 ohm
nickel, platinum, or
silicon)
2k ohm setpoint
potentiometers
0 to 10 VDC or
0 to 2 VDC
transmitters
Binary Inputs
4
(4) Dry contacts
(1) Momentary push
button from zone
sensor for temporary
occupancy mode
BI 4 may be used as
an accumulator input
for frequencies less
than 100 Hz.
4
(4) Dry contacts
(1) Momentary push
button from zone
sensor for temporary
occupancy mode
BI 4 may be used as
an accumulator input
for frequencies less
than 100 Hz.
4
(4) Dry contacts
(1) Momentary push
button from zone
sensor for temporary
occupancy mode
BI 4 may be used as
an accumulator input
for frequencies less
than 100 Hz.
Analog
Outputs
0/2
0 to 10 VDC
@ 10 mA
0/2
0 to 10 VDC
@ 10 mA
0/2
0 to 10 VDC
@ 10 mA
Binary
Outputs
8/6
24 VAC Triacs
@ 0.5 amperes
8/6
24 VAC Triacs
@ 0.5 amperes, or
0.8 amperes if total
power is limited
8/6
24 VAC Triacs
@ 0.5 amperes, or
0.8 amperes if total
power is limited
N2 Bus
Not Isolated * Isolated Isolated
Zone Bus
Discrete connections
at controller
Discrete connections
at controller
Discrete connections
at controller
8-pin phone jack on
controller
8-pin phone jack on
controller
8-pin and 6-pin phone
jack on controller *
6-pin phone jack at
zone sensor
6-pin phone jack at
zone sensor
6-pin phone jack at
zone sensor
LED Indication * LED Indication *
24 VAC Power
Terminations
Quick Connects
(Spade Lugs) *
Removable Screw
Terminal Block
Removable Screw
Terminal Block
I/O
Terminations
Quick Connects
(Spade Lugs)
Quick Connects
(Spade Lugs)
Fixed Screw Terminal
Block *
N2
Terminations
Fixed Screw Terminal
Block *
Removable Screw
Terminal Block
Removable Screw
Terminal Block
* VAV Controller model feature differences