jci-60152:a1 • 09/3/09 — Page 1 of 2
MPS-24A
Main Power Supply
jci-60152:a1
General
The MPS-24A is the main power supply for the IFC-2020/-1010,
XP Transponder or FC-2000 fire alarm control system. The
MPS-24A can also be used to power additional system equip-
ment such as the JNCA, JNCA-2, AMG and ACS series devices.
It provides all the necessary internal operating power plus addi-
tional power for operation of external alarm Notification Appli-
ance Circuits. A battery charging circuit is included.
Features
Provides all internal operating power for the system.
Up to 3.0 A of regulated, filtered alarm notification device
power available, compatible with any listed 24 VDC notifica-
tion appliance or any 24 VDC listed release solenoid.
Recharges standby batteries up to 55 AH in size.
Dual-rate charge capability.
Regulated and filtered four-wire detector power available
(depending on the system configuration).
Trouble LEDs for AC Power Fail, Battery, and Ground Fault
conditions.
Circuit breaker and automatically-resetting PTC resistors pro-
tect against current overload.
Power-limited on all external output power.
High-efficiency DC/DC converter for FACP internal +5 V
power.
High-efficiency switched regulator for notification appliance
power.
True battery supervision.
Optional battery backbox holds 55 AH batteries.
Applications
The MPS-24A Main Power Supply provides all of the required
internal system operating power, plus 3.0 A of regulated power
is available for external use.
Electrical Specifications
Primary Input Power: 120 volts, 50/60 Hz, 1.8 A maximum
(220 VAC option, model MPS-24AE).
Maximum Loading: of the 24 volt filtered regulated supply is
6.0 A (used for internal and external power where filtered regu-
lated power is required). Up to 3.0 A may be used to power Noti-
fication Appliance Circuits (NAC) or ACS Series annunciators.
Battery Charger: 24-volt float type, capable of charging 9 AH
to 55 AH batteries.
Brown-out and battery monitors
Trouble Indicators
AC POWER FAIL (LED #2) Indicates the loss of AC power,
low AC line or open circuit breaker
BATTERY (LED #3) Indicates battery failure
GROUND FAULT (LEDs 4 & 5) indicates a ground fault condi-
tion.
Installation
The MPS-24A power supply is installed in the lower bottom-left
corner of the CAB-A3/-A4, CAB-B3/-B4, CAB-C3/-C4, or CAB-
D3/-D4 enclosures. Screw terminals are provided for Earth
Ground; 120 or 220 VAC; Battery positive and negative; +24
VDC filtered, regulated, resettable power. Plug-in connectors
are provided for the Power Ribbon, Power Harness, and AVPS-
24 Supervision connection.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may be
in process. Consult factory for latest listing status.
UL Listed: S1570 (IFC-2020/-1010, FC-2000)
ULC Listed: CS118/CS733/CBP696 Vol. VII (IFC-2020, FC-
2000)
BSA: 578-81-SA
FM Approved (IFC-2020/-1010, FC-2000)
MEA: 289-91-E Vol VI (IFC-2020/-1010)
City of Denver (IFC-2020/-1010)
Product Line Information
MPS-24A: Main Power Supply. Includes 3.0 A of filtered, reg-
ulated audible/visual power.
MPS-24AE: Same as MPS-24A, but requires 220 VAC.
MPS-TR: Optional Main Power Supply Trouble Relay for
remote mounting of a stand-alone power supply. UL Listed.
Check with factory for additional listings and approvals.
JCI-LBB: Battery backbox, holds up to two BAT-12550 (55
AH) batteries.
JCI-LBBR: Same as JCI-LBB but painted red.
0713mps2.wmf

Other manuals for Johnson Controls MPS-24A

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls MPS-24A and is the answer not in the manual?

Overview

The MPS-24A is a main power supply designed for use with IFC-2020/-1010, XP Transponder, or FC-2000 fire alarm control systems. It can also power additional system equipment such as JNCA, JNCA-2, AMG, and ACS series devices. This unit provides all necessary internal operating power and additional power for external alarm Notification Appliance Circuits, and includes a battery charging circuit.

Function Description:

The MPS-24A serves as the primary power source for compatible fire alarm control systems and associated devices. It provides regulated and filtered power for both internal system operations and external notification appliances. A key feature is its ability to recharge standby batteries, ensuring continuous operation during power outages. The unit also incorporates various monitoring features to detect and indicate power-related issues.

Important Technical Specifications:

  • Primary Input Power: 120 volts, 50/60 Hz, 1.8 A maximum (for MPS-24A). An MPS-24AE model is available for 220 VAC input.
  • Maximum Loading: The 24-volt filtered regulated supply can provide up to 6.0 A, which is used for both internal and external power requirements. Up to 3.0 A of this can be dedicated to Notification Appliance Circuits (NAC) or ACS Series annunciators.
  • Notification Appliance/Annunciator Power: Provides 3.0 A (in alarm max) of power that is power-limited, filtered, regulated, and non-resettable. This output can also be used for ACS series annunciators. A jumper (JP5) can be cut to convert this output to a resettable, 2 A maximum circuit.
  • Four-Wire Smoke Detector/Annunciator Power: Offers 24 VDC (20.4-26.4 V, 200 mV ripple), 1 amp max. This power is filtered, regulated, resettable, and power-limited, but requires supervision via a UL approved Power Supervision Relay.
  • Battery Charger: A 24-volt float type charger capable of charging 9 AH to 55 AH batteries. It features dual-rate charge capability.
  • DC/DC Converter: High-efficiency DC/DC converter for FACP internal +5 V power.
  • Switched Regulator: High-efficiency switched regulator for notification appliance power.
  • Output Protection: Circuit breaker and automatically-resetting PTC resistors protect against current overload. All external output power is power-limited.

Usage Features:

  • Versatile Power Output: Provides regulated, filtered alarm notification device power compatible with any listed 24 VDC notification appliance or 24 VDC listed release solenoid.
  • Battery Management: Recharges standby batteries up to 55 AH in size with dual-rate charge capability and includes true battery supervision. An optional battery backbox (JCI-LBB) can hold up to two BAT-12550 (55 AH) batteries.
  • Detector Power: Offers regulated and filtered four-wire detector power, depending on the system configuration.
  • Installation: The MPS-24A is designed for installation in the lower bottom-left corner of CAB-A3/-A4, CAB-B3/-B4, CAB-C3/-C4, or CAB-D3/-D4 enclosures. Screw terminals are provided for Earth Ground, 120 or 220 VAC, Battery positive and negative, and +24 VDC filtered, regulated, resettable power. Plug-in connectors are used for the Power Ribbon, Power Harness, and AVPS-24 Supervision connection.
  • Optional Equipment:
    • MPM-2 Main Power Meter: Provides battery voltage and charging current meters, mounting hardware, and cable for enhanced monitoring.
    • MPS-TR Optional Main Power Supply Trouble Relay: For remote mounting of a stand-alone power supply.
    • JCI-LBB(R) Battery Backbox: Holds up to two BAT-12550 (55 AH) batteries. The JCI-LBBR is a red-painted version.

Maintenance Features:

  • Trouble Indicators: The unit includes several LEDs for quick identification of issues:
    • AC POWER FAIL (LED #2): Indicates loss of AC power, low AC line, or an open circuit breaker.
    • BATTERY (LED #3): Indicates battery failure.
    • GROUND FAULT (LEDs 4 & 5): Indicates a ground fault condition.
  • Brown-out and Battery Monitors: Integrated monitoring systems for detecting power fluctuations and battery status.
  • Earth Fault Detection: A jumper (R27) can be cut to disable Earth Fault Detection if needed.
  • Notification Appliance Power Circuit Configuration: Jumper JP5 can be cut to make the notification appliance power on TB3 terminals 3 and 4 a resettable, 2-amp maximum circuit. Jumper JP2 must be cut, otherwise a short on the notification appliance power circuit (terminals 3 and 4) would register incorrectly as loss of primary (AC) power (IFC-2020/-1010 only).

Johnson Controls MPS-24A Specifications