P/N 51870:G • ECN 08-704
Document 51870
04/23/2009
Intelligent Control Panel
SLC
Wiring Manual

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC2-640 and is the answer not in the manual?

Johnson Controls IFC2-640 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC2-640
CategoryControl Panel
LanguageEnglish

Summary

Fire Alarm System Limitations

Important Smoke Detector Installation

Smoke detectors must be installed in rooms used for system connection.

Strobe-Induced Seizures Warning

Strobes can cause seizures in people with epilepsy under certain circumstances.

Audible Warning Device Hearing Loss

Warning devices can cause temporary or permanent hearing loss.

Installation Precautions

System Re-acceptance Testing

System must be tested per NFPA 72 after any programming or component changes.

Disconnect Power Before Servicing

Disconnect AC power and batteries before removing or inserting circuit boards.

Follow Manual Instructions

Follow installation, operating, and programming manual instructions to avoid damage.

Section 2: Wiring Requirements

Recommended SLC Wiring

Provides guidance on wire types, distances, and resistance limits for SLC loops.

Two-Wire SLC - Style 4 (Class B)

Details wiring requirements for two-wire Style 4 SLC configurations.

Four-Wire SLC Style 6 & 7 (Class A)

Details wiring requirements for four-wire Style 6 & 7 SLC configurations.

Control Panel Terminal Blocks

Shows terminal block connections for various control panels.

Section 3: Shielded Wire Termination

Section 4: SLC Circuits without Isolators

Section 5: SLC Circuits with Isolators

Fault Isolator Module

Monitors SLC for short circuits and disconnects faulted branches.

Isolator Detector Bases

Isolator bases prevent loop disabling from short circuits.

Setting an SLC Address for a Module

NFPA Style B IDC Using Monitor Modules

NFPA Style D IDC Using Monitor Modules

NFPA Style B IDC Using Dual Monitor Modules

NFPA Style B IDC Using Zone Interface Modules

NFPA Style D IDC Using Zone Interface Modules

Section 7: Control Modules

Wiring NACs with Control Modules

Shows connections for M300CJ module to power a 24 VDC NAC.

Wiring Solenoids with M300 CJ-REL

Shows connections for M300CJ-REL module to a solenoid.

Wiring Style Y NAC (Two-Wire)

Shows supervised, power-limited Style Y NAC wiring using M300CJ.

Wiring Style Z NAC (Four-Wire)

Shows supervised, power-limited Style Z NAC wiring using M300CJ.

Connecting Releasing Devices

Details connecting releasing devices to the M300CJ-REL module.

Appendix A: Power Considerations

Supplying Power to Detectors and NACs

Calculations for allowable resistance and wire size for 24 VDC power runs.

Appendix B: SLC Surge Suppression

SLC Surge Suppressor Installation

Instructions for mounting and connecting secondary surge suppressors.

DTK-2 LVLP-F and PLP-42 N Connections (IFC-200)

Shows connections for DTK-2LVLP-F and PLP-42N suppressors with IFC-200.

Surge Suppressor Connections (IFC-300;400)

Shows connections for SLCP-30, DTK-2LVLP-F, PLP-42N with IFC-300/400.