10 MR4PMUHV Electronic Temperature/Defrost Control with Relay Pack Product/Technical Bulletin
Table 4: Function Settings in Order of Programming in Control Module
Useable Setting Range and Unit Value
-40 to 99°F (-40 to 80°C)
-40°F (-40°C) to
High Setpoint Stop
Low Setpoint Stop to
99°F (80°C)
0 = electric defrost
1 = hot gas defrost
0 = time-based
1 = temperature-based
Defrost Termination Temperature
0 = last main sensor reading
1 = main setpoint
0 (last main sensor
reading)
Display Delay After Defrost
0 = no response
1 = compressor off, alarm on
2 = alarm on
3 = evap. fan off, alarm on
0 = parallel with compressor
1 = always on
0 (parallel with
compressor)
0 = compressor on
1 = compressor off
2 = based on last four cycles
2 (based on last four
cycles)
Temperature Sensor Offset
-20 to 20F° (-20 to 20C°)