EasyManua.ls Logo

Johnson Controls MR4PMUHV - Function Settings Reference; Programming Control Module Functions

Johnson Controls MR4PMUHV
13 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 MR4PMUHV Electronic Temperature/Defrost Control with Relay Pack Product/Technical Bulletin
Table 4: Function Settings in Order of Programming in Control Module
Display
Code
Function
Useable Setting Range and Unit Value
Factory-Set Values
(None)
Setpoint
-40 to 99°F (-40 to 80°C)
HY
Differential
1 to 9F° (1 to 9C°)
5 (F°)
LL
Low Setpoint Stop
-40°F (-40°C) to
High Setpoint Stop
-25 (°F)
HL
High Setpoint Stop
Low Setpoint Stop to
99°F (80°C)
40 (°F)
CC
Cycle Delay
0 to 9 minutes
1 (minutes)
Co
Deep Freezing Time
0 to 99 minutes
60 (minutes)
AH
High Temperature Alarm
0 to 50F° (0 to 50C°)
10 (F°)
AL
Low Temperature Alarm
-50 to 0F° (-50 to 0C°)
-10 (F°)
Ad
Alarm Differential
1 to 9F° (1 to 9C°)
5 (F°)
At
Alarm Time Delay
0 to 99 minutes
3 (minutes)
dF
Defrost Mode
0 = electric defrost
1 = hot gas defrost
0 (electric defrost)
dE
Defrost Termination Mode
0 = time-based
1 = temperature-based
1 (temperature-based)
dt
Defrost Termination Temperature
32 to 68°F (0 to 20°C)
55 (°F)
di
Defrost Interval
1 to 99 hours
7 (hours)
dd
Maximum Defrost Duration
0 to 99 minutes
45 (minutes)
dC
Dripping Time
0 to 99 minutes
5 (minutes)
dU
First Defrost Delay
OF, 0 to 99 minutes
OF (Off)
dP
Display During Defrost
0 = last main sensor reading
1 = main setpoint
0 (last main sensor
reading)
dr
Display Delay After Defrost
1 to 99 minutes
20 (minutes)
iF
Binary Input Mode
0 = no response
1 = compressor off, alarm on
2 = alarm on
3 = evap. fan off, alarm on
0 (no response)
id
Binary Input Time Delay
0 to 99 minutes
0 (minutes)
FF
Fan Operating Mode
0 = parallel with compressor
1 = always on
0 (parallel with
compressor)
Fd
Fan Startup Delay
0 to 99 minutes
5 (minutes)
Fr
Fan Start Temperature
-22 to 41°F (-30 to 5°C)
40 (°F)
SF
Sensor Failure Operation
0 = compressor on
1 = compressor off
2 = based on last four cycles
2 (based on last four
cycles)
So
Temperature Sensor Offset
-20 to 20F° (-20 to 20C°)
0 (F°)
Un
Temperature Units Used
0 = °C
1 = °F
1 (°F)
PU
Display Refresh Rate
1 to 99 seconds
1 (second)