MR4PMUHV Electronic Temperature/Defrost Control with Relay Pack Product/Technical Bulletin 11
Alarm and Fault Display Codes
These alarm and fault codes flash on the LED
display when the control detects the following faults.
Table 5: Display Codes and Status
Display
Code
Alarm or Fault Condition
System Status
F1
Indicates an open or shorted main temperature
sensor.
Alarm is on. Compressor runs according to the Sensor Failure
Mode selected. Correct problem with sensor and cycle power
to reset control.
F2
Indicates an open or shorted evaporator
temperature sensor.
Alarm is on. Defrost cycle is controlled by Defrost Interval and
Defrost Duration. Correct problem with sensor to reset control.
A1
Binary input is open for longer than the Binary
Input Time Delay and Binary Input Mode
Option 1 is selected.
Alarm is on. Compressor, Defrost, and Evaporator Fan are
off.
A2
Binary input is open for longer than Binary Input
Time Delay and Binary Input Mode Option 2 is
selected.
Alarm, Compressor and Evaporator Fan are on. Defrost may
be on or off.
A3
Binary input is open for longer than the Binary
Input Time Delay and Binary Input Mode
Option 3 selected.
Alarm and Compressor are on. Evaporator Fan is off. Defrost
may be on or off.
HI
Main sensor temperature has reached or
exceeded the High Temperature Alarm value.
Alarm is on. Correct problem to reset control.
LO
Main sensor temperature has reached or fallen
below the Low Temperature Alarm value.
Alarm is on. Correct problem to reset control.
EE
Indicates program failure.
Alarm is on. Other outputs are off. Replace control.
Ordering Information
Table 6: Ordering Information
Item Code
Description
Shipping Weight
MR4PMUHV-12C
Relay pack temperature/defrost control with two A99B sensors
2.9 lb (1320 g)
MR4PM12C-12C
Replacement control module for use in relay pack only
1.6 lb (726 g)
RP4MRUHV-1C
Relay pack without control module
2.3 lb (1060 g)
A99BB-200C
Sensor, cable length: 6-1/2 ft (2 m)
0.13 lb (60 g)
Repair and Replacement
Field repair of the control should not be made. In case
of a defective or improperly functioning control, please
contact your nearest Johnson Controls/PENN™
representative.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls MR4PMUHV and is the answer not in the manual?

Johnson Controls MR4PMUHV Specifications

MR4PMUHV-12C

Power IconPower
frequency60 Hz
power consumption5VA @240, 5VA @120
Operating Environment IconOperating Environment
ambient operating conditions+14 to +111°F (-10 to +44°C); derate 6.25% per 1°C from 45°C to 60°C; 0 to 95 % RH (non-condensing)
ambient storage conditions-22 to +176°F (-30 to +80°C); 0 to 95 % RH (non-condensing)
accuracy± 1.8F° ( ± 1C°)
Weight and Dimensions IconWeight and Dimensions
dimensions7.94 x 3.6 x 2.4 in. (202 x 92 x 61 mm)
shipping weight2.9 lb (1320g)
A99 sensor cable length6.6 ft (2m)

MR4PM12C-12C

Operating Environment IconOperating Environment
ambient operating conditions+14 to +140°F (-10 to +60°C); 0 to 95 % RH (non-condensing)
ambient storage conditions-22 to +176°F (-30 to +80°C); 0 to 95 % RH (non-condensing)
accuracy± 1.8F° ( ± 1C°)

RP4MRUHV-1C

Operating Environment IconOperating Environment
ambient operating conditions-40 to +111°F (-40 to +44°C); derate 6.25% per 1°C from 45°C to 60°C; 0 to 95 % RH (non-condensing)
ambient storage conditions-40 to +185°F (-40 to +85°C); 0 to 95 % RH (non-condensing)
accuracy± 1.8F° ( ± 1C°)