EasyManua.ls Logo

Johnson Controls MS-NAE5510-3 - Page 7

Johnson Controls MS-NAE5510-3
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting LonWorks devices
About this task:
To connect LonWorks devices, complete the following
steps:
1. Connect the 2-wire cable from the LonWorks trunk
to the removable 3-terminal blue plug labeled LON
(Figure 3). The LonWorks network trunk is available
on the MS-NAE5520-3 model only.
Figure 9: LonWorks network terminal block and wiring
connections
Table 4: LON trunk terminal block wiring
Callout Description
1 LonWorks network terminal block
2 LonWorks network terminal block plug
3
Terminating wires (2-wire cable shown)
Note: LonWorks network wires are not polarity
sensitive.
2. To add additional vendor devices, wire from one
device to the next in a daisy-chained fashion. Do not
connect more than two wires to each terminal.
Connecting Modbus RTU devices
About this task: The network engine connects to
Modbus RTU devices directly if the RS485 protocol is in
use or by using a converter if the RS-232 protocol is in
use. (After installation and wiring are complete, refer
to the Network Engine Commissioning for Modbus Vendor
Integration Application Note (LIT-12013150) for additional
information.)
1. For a Modbus RTU device that requires an RS-485
connection, terminate the 2-wire bus cable from
the Modbus device to one of the removable 4-
terminal blue plugs on the network engine, labeled
FC-A and FC-B (Figure 10).
Figure 10: FC Bus terminal block and wiring connections
for Modbus
Table 5: FC Bus terminal block wiring for Modbus
Callout Description
1 FC Bus terminal block
2 FC Bus terminal block plug
3 Terminating wires for Modbus (2-wire cable shown)
2. For a Modbus RTU device that requires an RS232C
serial connection, use a cable to connect the
converter to either the RS232C A or RS232C B serial
port on the network engine. The maximum cable
length between devices connected though an
RS-232 line depends on the baud rate used. In
general, the cable should not exceed 15 meters for
9600 baud.
3. Wire from the RS-485 terminal on the converter to
the RS-485 port on the vendor device (Figure 11).
The RS-485 bus is a two-wire network.
a. Connect the converter's + A terminal to the
device's + (or A) terminal.
b. Connect the converter's - B terminal to the
device's - (or B) terminal.
Figure 11: Connection between converter and device
4. To add additional vendor devices, wire from one
device to the next in a daisy chain configuration.
The completed wiring should look similar to Figure
12.
NAE55 Installation Guide 9

Related product manuals