EasyManua.ls Logo

Johnson Controls NS Series - Setup and Adjustments; LCD Display and Controls; Temperature and Occupancy Control; Configuration and Addressing

Johnson Controls NS Series
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
About this task:
Table 2: Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD
Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
Temperature Only
Models
21 mA Maximum (Non-transmitting)Current Consumption
Temperature and
Humidity Models
25 mA Maximum (Non-transmitting)
Terminations Modular Jack or Screw Terminal Block
NS-BHx7x03-x, NS-
BPB7003-x, NS-
BTx7003-x, Models
DIP Switch Set from 200 to 203; Factory Set at 203Network Sensor
Addressing
All Other Models Fixed Address of 199
Modular Jack
Models
24 or 26 AWG (0.5 or 0.4 mm Diameter); Three Twisted Pair (Six
Conductors)
Wire Size
Screw Terminal
Block Models
18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter)
Recommended
Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Temperature Measurement Range 32.0°F/0.0°C to 104.0°F/40.0°C
Full Range 0 to 100% RHHumidity Measurement
Range
Calibrated Range 10 to 90% RH
Temperature Sensor Type Local 1k Ohm Platinum Resistance Temperature Detector (RTD);
Class A per IEC 60751
Humidity Sensor Type Thin Film Capacitive Sensor
Temperature Resolution ±0.5F°/±0.5C°
NS Series Network
Zone Sensor
±1.0F°/±0.6C°Temperature Accuracy
Temperature
Element Only
0.35F° at 70°F (0.19C° at 21°C)
NS-BPB700x-x
Models
±2% RH for 20 to 80% RH at 50°F to 95°F (10°C to 35°C);±4% RH for 10
to 20% and 80 to 90% RH at 50°F to 95°F (10°C to 35°C)
Humidity Element
Accuracy
NS-BHx7x0x-x
Models
±3% RH for 20 to 80% RH at 77°F (25°C)±6% RH for 10 to 20% and 80
to 90% RH at 77°F (25°C)
Time Constant 10 Minutes Nominal at 10 fpm Airflow
Default Temperature Setpoint Adjustment
Range
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° Increments
Operating 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing;85°F (29°C)
Maximum Dew Point
Ambient Conditions
Storage -4 to 140°F (-20 to 60°C); 5 to 95% RH, Noncondensing
BACnet
International
BACnet Testing Laboratories
(BTL) 135-2004 Listed BACnet Smart
Sensor (B-SS)
Note: Excludes the NS-BTV700x-0 models.
UL Listed, File E107041, CCN PAZX,Under UL 916, Energy
Management Equipment
United States
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
UL Listed, File E107041, CCN PAZX7,Under CAN/CSA C22.2 No. 205,
Signal Equipment
Compliance
Canada
Industry Canada, ICES-003
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD Installation Guide 5

Other manuals for Johnson Controls NS Series

Related product manuals