Technical Specifications
About this task:
Table 2: Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD
Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
Temperature Only
Models
21 mA Maximum (Non-transmitting)Current Consumption
Temperature and
Humidity Models
25 mA Maximum (Non-transmitting)
Terminations Modular Jack or Screw Terminal Block
NS-BHx7x03-x, NS-
BPB7003-x, NS-
BTx7003-x, Models
DIP Switch Set from 200 to 203; Factory Set at 203Network Sensor
Addressing
All Other Models Fixed Address of 199
Modular Jack
Models
24 or 26 AWG (0.5 or 0.4 mm Diameter); Three Twisted Pair (Six
Conductors)
Wire Size
Screw Terminal
Block Models
18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter)
Recommended
Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Temperature Measurement Range 32.0°F/0.0°C to 104.0°F/40.0°C
Full Range 0 to 100% RHHumidity Measurement
Range
Calibrated Range 10 to 90% RH
Temperature Sensor Type Local 1k Ohm Platinum Resistance Temperature Detector (RTD);
Class A per IEC 60751
Humidity Sensor Type Thin Film Capacitive Sensor
Temperature Resolution ±0.5F°/±0.5C°
NS Series Network
Zone Sensor
±1.0F°/±0.6C°Temperature Accuracy
Temperature
Element Only
0.35F° at 70°F (0.19C° at 21°C)
NS-BPB700x-x
Models
±2% RH for 20 to 80% RH at 50°F to 95°F (10°C to 35°C);±4% RH for 10
to 20% and 80 to 90% RH at 50°F to 95°F (10°C to 35°C)
Humidity Element
Accuracy
NS-BHx7x0x-x
Models
±3% RH for 20 to 80% RH at 77°F (25°C)±6% RH for 10 to 20% and 80
to 90% RH at 77°F (25°C)
Time Constant 10 Minutes Nominal at 10 fpm Airflow
Default Temperature Setpoint Adjustment
Range
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° Increments
Operating 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing;85°F (29°C)
Maximum Dew Point
Ambient Conditions
Storage -4 to 140°F (-20 to 60°C); 5 to 95% RH, Noncondensing
BACnet
International
BACnet Testing Laboratories
™
(BTL) 135-2004 Listed BACnet Smart
Sensor (B-SS)
Note: Excludes the NS-BTV700x-0 models.
UL Listed, File E107041, CCN PAZX,Under UL 916, Energy
Management Equipment
United States
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
UL Listed, File E107041, CCN PAZX7,Under CAN/CSA C22.2 No. 205,
Signal Equipment
Compliance
Canada
Industry Canada, ICES-003
Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD Installation Guide 5