5.2 PRINT Key
The 'PRINT' key allows the operator to obtain a printout
of real-time system operating data or a printout of
system data at the "instant of the fault" on the last six
faults which occurred on the unit. An optional printer is
required for the printout.
Operating Data Print-out
Pressing the 'PRINT' key and then 'OPER DATA' key
allows the operator to obtain a printout of current system
operating parameters. When the 'OPER DATA' key is
pressed, a snapshot will be taken of system operating
conditions and panel programming selections. This data
will be temporarily stored in memory and transmission of
this data will begin to the printer. A sample operating
data printout is shown opposite.
1-22
Form 201.26.OI1(11/09)
YORK INTERNATIONAL CORPORATION
MILLENNIUM LIQUID CHILLER
UNIT STATUS
10:01AM 11 APR 08
SYS 1 COMPRESSORS RUNNING 2
SYS 2 COMPRESSORS RUNNING 3
OPTIONS
CHILLED LIQUID WATER
LOCAL/REMOTE MODE REMOTE
LEAD/LAG CONTROL AUTOMATIC
POWER FAIL RESTART MANUAL
EXPANSION VALVE THERMOSTATIC
REMOTE TEMP RESET 0 TO 10 V
YORK HYDRO KIT PUMPS = 1
HOT GAS BYPASS TYPE NONE
PROGRAM VALUES
DSCH PRESS CUTOUT 38.6 BARG
SUCT PRESS CUTOUT 5.59 BARG
LOW AMBIENT CUTOUT -3.9 DEGC
LEAVING LIQUID CUTOUT 3.0 DEGC
ANTI RECYCLE TIME 600 SECS
FAN CONTROL ON PRESS 23.1 BARG
FAN DIFF OFF PRESS 5.5 BARG
NUMBER OF COMPRESSORS 6
SYS1 NUMBER OF FANS 4
SYS2 NUMBER OF FANS 4
REFRIGERANT TYPE R-410A
REMOTE UNIT ID PROGRAMMED 0
RATE SENSITIVITY 2.0 DEGC/MIN
RATE CONTROL RANGE TMP 6.1 DEGC
UNIT DATA
RETURN LIQUID TEMP 11.2 DEGC
LEAVING LIQUID TEMP 6.2 DEGC
COOLING RANGE 6.1 +/- 1.1 DEGC
REMOTE SETPOINT 6.1 DEGC
AMBIENT AIR TEMP 11.3 DEGC
LEAD SYSTEM SYS 2
EVAPORATOR PUMP ON
EVAPORATOR HEATER OFF
ACTIVE REMOTE CONTROL TEMP
EVAP PUMP TOTAL RUN HOURS 83
SOFTWARE VERSION C.M17.16.02
SYSTEM 1 DATA
COMP STATUS 1=OFF 2=ON 3=ON
RUN TIME 0- 1- 8-33 D-H-M-S
SUCTION PRESSURE 8.14 BARG
DISCHARGE PRESSURE 24.4 BARG
LIQUID LINE SOLENOID ON
CONDENSER FAN STAGE LO 4
SYSTEM 2 DATA
COMP STATUS 1=ON 2=ON 3=ON
RUN TIME 0- 1-13-44 D-H-M-S
SUCTION PRESSURE 7.45 BARG
DISCHARGE PRESSURE 27.1 BARG
LIQUID LINE SOLENOID ON
CONDENSER FAN STAGE HI 4
DAILY SCHEDULE
SMTWTFS *=HOLIDAY
SUN START=00:00AM STOP=00:00AM
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM