ZFR1800 Series Wireless Field Bus System Technical Bulletin52
4. Expand the Field Bus and the MS-ZFR1810-0 Coordinator items as shown in
Figure 19. Open the details window for the ZIGBEE item.
5. Click Edit and change the Network Optimize or Network Reform field to
TRUE.
Note: In Release 4.1, the Network Optimize field is labeled Route Repair
and the Network Reform field is labeled Text Not Found.
6. Click Relearn. All devices on the wireless network go offline.
7. Allow up to 15 minutes for the WEFCs to rejoin the network. Sensors may take
an additional 45 minutes to rejoin the network.
8. Verify that all devices on the wireless network report online to the NAE/NCE.
If one or more devices are not online, see Troubleshooting
.
Figure 19: Optimizing/Reforming a Network from the Metasys Site