2 DMS1.1 / DM1.1 / DML1.1 Proportional Actuators
Installation and adjustment
Figure 3: Mounting Instructions
Installation
Attach the actuator to the damper spindle by means of the adapter and
secure the locking device with the screws provided.
Angle of rotation limiting
An angle-of-rotation/working range (Figure 2 g1.) of less than 90° can be
limited mechanically by repositioning the adapter in 5° steps as required.
The adapter is released by simply pressing the adapter clips on the lower
side of the actuator (Figure 2 g2.).
Selecting the direction of rotation
In order to reverse the direction of rotation (CW/CCW), loosen screw
(See Figure 1 a.) and remove the cover.
The direction of rotation can be reversed with the switch (See Figure 2 d.).
Factory setting: Clockwise (CW) rotation.