IMPORTANT: READ THIS FIRST
DO NOT EXPOSE THE E30 TO VIBRATION. INSTALL ONLY IN
PIPEWORK THAT DOES NOT VIBRATE. Vibration will damage the
electronics within the E30 and will void your product warranty.
This E30 digital pressure switch has been fully tested and calibrated. It is
set to use kPa in mode 1 and it has its start-up and run-on timers both set
to 5 seconds. It is set to close relay 1 at 100kPa and open it at 200 kPa.
All other functions are turned off. On start up, the E30 will run a pump
connected to relay 1, using its start-up timer. If it fi nds pressure in the pipe
system it will continue to run the pump. If pressure is lost, the pump will
continue to run for 5 seconds, held on by the E30’s run-on timer. If pressure
fails to return, the pump will be shut down after the run-on period. Pressing
and releasing the (R) button on the E30 will repeat this basic process.
THE BUTTONS
The E30 is controlled and confi gured using 4 onboard buttons.
(R) Reset button. Stops the pump(s) and restarts the E30 when released.
(˄) Up arrow button. For increasing program settings.
(˅) Down arrow button. For decreasing program settings.
(P) Programming button. For stepping through the menu and entering
settings into memory.
THE LIGHTS
The E30 includes 3 multicolour lights to indicate activity.
Pump: This light is GREEN when a pump is running and RED when the
pump is stopped.
Timer: This light may be
GREEN or RED when a timer or special function
is running.
Remote: This light is
BLUE when the remote input is closed and off when
the remote is open.