Installation
Version: ECO_M_ENG_220303_E002
4.3. Ex Installation
The ECO ... -Ex are only intrinsically safe if they are operated via isolating amplifiers or supply isolators. The
technical specifications in the document "T100 Control drawing for hazardous areas" must be observedT100 must
be observed
For mechanical installation, follow the installation instructions in chapter 4.1.
Connect the ECO to isolating amplifiers using a shielded cable.
Auswahl Barrieren
Cable 4x0.25 single-core screen
Unitronic LiYCY CY 4x0,25
Additional conditions for North American CSA certification:
Only ECOs with product code T*10 and an M12 stainless steel plug, can be used as Type 3 for outdoor use. All
other configurations may only be used indoors.
WARNING!
Explosion hazard
• The technical specifications in the document "T100 Control drawing for hazardous areas" must be observed.
• When used in potentially explosive atmospheres, the ECO must be operated via suitable isolating amplifiers
or ten barriers.
• To avoid a possible ignition hazard, the versions with aluminum housing must not be exposed to shocks or
friction from other components.
NOTE:
• The installation of the ECO in potentially explosive atmospheres must be carried out by appropriately
trained personnel.
• If the installation is not carried out in accordance with the manufacturer's specifications, the safety for the
corresponding type of protection is invalidated.
• When using long connecting cables, ensure that the maximum capacities and inductances for the
corresponding voltage and gas group are not exceeded.
• If the housing of the ECO is opened by unauthorized personnel, the safety for the corresponding ignition
protection type is void.
• Repairs may only be carried out by the manufacturer.