Clamp-on Flow Sensor
FD-Q Series
Setting Guide
For precautions and operation details,
refer to the instruction manual included with the product.
Output 1 indicator
Output 2 indicator
M12-4pin
connector
Stability indicator
Detection stability
1 to 4 indicator lights Stability level display
1 blinking indicator light Detection not possible
Current value display Set value display
Setting button ()
Setting button ()
Large status
indicator
Lights up according to the
owing status of uid.
MODE button (
MODE
)
Bracket Set-Up
The bracket provided with each unit is
adjustable between the two supported
pipe diameters (ex. FD-Q10C on the
right).
Simply rotate the bottom half 180° to
switch the bracket diameter.
(1) 1/4'' (8 A) (2) 3/8'' (10 A)
180 degrees inversion
Initializing (Factory Default)
To initialize, press the arrow 5 times while holding
down the MODE button.
From this screen simply arrow up to "yes" and press
MODE to select.
Press MODE once more to complete initialization.

Initialization performed
Selecting the Flow Units
(Gallons or Liters)
After initialization or upon start-up, it is possible to change the units.
Simply press and hold the MODE and buttons while on the PNP/NPN
selection screen.
Calibration
Set-value
To calibrate the sensor, simply press (and/
or hold) the or arrows to change the
set-value.
* Image represents default display for standard
detection.
Stability Check
Stable Unstable
If the stability indicator shows 1-indicator light or 1-blinking indicator light, the
detection stability is low.
Stability may improve by changing the installation condition.
See "Troubleshooting (P4)".
Start-Up/Initialization Settings
Reference
To return to a previous screen, press
MODE
+ .
When
MODE
+ + are pressed simultaneously in this menu,
the quick setting code can be entered.
MODE
MODE
MODE
MODE
MODE








A. Selecting NPN/PNP (Press or to select.)
 NPN output
 PNP output
C. Selectingowdirection(Press or to select.)
"rEu" is displayed if the wrong ow direction is selected.
r Flow direction: From left to right
 Flow direction: From right to left
D. Selecting bore diameter of pipe (Press or to select.)
Please conrm if the direction and setting of the FD-Q metal tting
match.
Model Selection NPS DN
FD-Q10C
1/4" 8 A
3/8" 10 A
FD-Q20C
1/2" 15 A
3/4" 20 A
FD-Q32C
1
1" 25 A
1 1/4" 32 A
FD-Q50C
1 1/2" 40 A
2
2" 50 A
B. Selecting ch.1 and ch.2 functions (Press or to select.)
Selection Mode ch.1 (pin (4)) ch.2 (pin (2))
A

1 Control Output Mode Control output
B
u
2 Control Output Mode Control output Control output
C

Control Output +
External Input Mode
Control output External input
D

Control Output +
Analog Output Mode
Control output Analog output
Initial setting complete
To Provide Better Flow Readings
MODE
MODE
MODE
MODE
MODE
MODE














MODE
Press and hold
E. Correctingtheowratevalue
(Press or to select.)

No correction
E
Selecting pipe schedule

Setting ow rate magnication
(Span adjustment)
Initial setting complete
Initial setting complete Initial setting complete
Selecting pipe schedule
Selecting the pipe thickness
(schedule) correctly will
improve ow rate readings.
(Press or to select.)

SGP
2
Sch.20

Sch.40

Sch.80
Adjustingowratespan
The ow rate values can
be adjusted by 0.1x to 2.5x
the initial values of the
instantaneous ow rate value
detected by the FD-Q Series.
(Press or to select.)
Setting range: 0.10 to 2.50
Selecting the Flow Units
MODE

MODE
+ Press and hold
F. Selecting the units
liter
gallon

Other manuals for Keyence FD-Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Keyence FD-Q Series and is the answer not in the manual?

Keyence FD-Q Series Specifications

General IconGeneral
BrandKeyence
ModelFD-Q Series
CategoryAccessories
LanguageEnglish

Related product manuals