18
10. Troubleshooting
iLEDs Sounder Unit Status Action
Error condition -1
Red Flashing every 30 secs
Chirp/30 secs Unit has failed Replace
Amber Flashing every 30 secs
Error condition -2
Red ON
Constant lound
sound
Unit microprocessor has failed Replace
Amber
End of Life
Red Flashing
Chirp twice every
30 seconds
The unit has reached the end
of its life
Replace
Amber
Flashing twice every
30 secs
Low battery
Red Flashing every 15 secs
Chirp/15 secs Backup battery is discharged
Ensure switch is ON at
the rear of the unit-if it
persists, contact
customer service.
Amber Flashing every 15 secs
NOTE: If AC mains is connected and active, the Green LED will be on continuous. If Green LED is not on, see Section 6.