4. Installation Instructions – Recommended Locations
NOTE: CO alarms should be installed following the guidance of relevant local standards, such as EN 50292.
Whether the alarm is wall-mounted or ceiling mounted, place the alarm a horizontal distance of between 1 metre
and 3 metres from a fuel burning appliance.
When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a minimum of 150 mm
below the ceiling, and the bottom edge of the alarm within 300 mm below the ceiling. The bottom of the alarm
should also be at a level greater than the height of any door or window.
Locate within hearing distance of bedrooms* and place at sleeping height if a heating appliance is in the bedroom.
CO alarms in rooms with sloped ceilings should be located on the high side of the room.
Ceiling mounted alarms should be at least 300 mm from any wall.
If there is a partition in the room, locate the alarm on the same side of the partition as the potential source.
* A CO alarm should be installed in all rooms containing a fuel burning appliance. Additional CO alarms should be
installed in rooms where most awake time is spent, in every sleeping area, and on every level of the home.