2 / 2 P/N 3102737-EN • REV 004 • ISS 25MAY22
To perform a sensor function test:
1. If supported by the control unit, ready the initiating device circuit for
testing. Refer to the control unit’s technical reference manual for
instructions.
2. Activate the smoke sensor using No Climb Products model Smoke
Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol
spray, a smoke generator, or the Testifire detector tester per the
manufacturer’s instructions.
Maintenance
To ensure proper operation, plan maintenance (regular or selected) of
the detector in accordance with the AHJ and all applicable governing
laws, codes, or standards. Refer to CAN/ULC-S536 Standard for the
Inspection and Testing of Fire Alarm Systems and NFPA 72 National
Fire Alarm and Signaling Code.
Refer to application bulletin P/N 3102650 for additional information and
cleaning instructions.
Specifications
Operating voltage
6.5 to 33 VDC
Current
Standby
Alarm
88 µA at 18 VDC
145 µA at 33 VDC
60 mA (max.) if not limited by
control unit
Remote LED output
0.225 mA average
(50 msec ON, 1 sec OFF)
Reset voltage
2.5 V, maximum
Reset time
1 second, minimum
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Sensitivity
0.5 to 4.36 %/ft. obscuration
(1.63 to 13.62 %/m)
Air velocity
0 to 4,000 ft./min (0 to 20.32 m/s)
Environmental compensation
Automatic
Response time index
(evaluated by FM Approvals)
Quick
Wall mounting: distance from
ceiling
12 in. (305 mm) max.
Compatible bases
KC2 series standard and relay
bases
Compatible detector testers
[1] Testifire 1000, Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 100°F (0 to 38°C)
0 to 93% noncondensing
Storage temperature
4 to 140°F (−20 to 60°C)
[1] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
Regulatory Information
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not
cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Compatibility
identifier
S10A R2
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.kidde-esfire.com.