Chapter 6: Preventive maintenance and testing
P/N 3101890-EN • REV 006 • ISS 21JUN18 113
Detector component replacement procedures
V-PCOS smoke chamber
V-PCOS smoke detectors have a replaceable smoke chamber. Replace the chamber with model number 2-
SPRC2 if the control panel still indicates a dirty detector after cleaning the detector. Refer to the 2-SPRC2 Smoke
Chamber Replacement Installation Sheet (P/N 3101596) for instructions.
CO sensor module
CO detectors use a 2-CORPL replacement sensor. Replace the sensor every six years from the date of
manufacture or when the control panel indicates a sensor end-of-life condition, whichever comes first. Refer to the
2-CORPL CO Replacement Module Installation Sheet (P/N 3101589) for instructions.
Note: For proper operation, never replace the CO sensor without also replacing the PCB because each board
has calibration data specific to the matching CO sensor.
Maintenance schedule
Table 39: Routine maintenance schedule
Component
Frequency
Control equipment [1]
Quarterly/Annually
Supervisory signal devices (except valve tamper switches)
Quarterly
Off
-premises transmission equipment Quarterly
Waterflow devices
Semiannually
Valve tamper switches
Semiannually
Batteries [2]
Annually
Control unit trouble signals
Annually
Fiber optic cable connections
Annually
Emergency voice/alarm communication equipment
Annually
Remote annunciators
Annually
Smoke detectors
Annually
Heat
detectors Annually
Fire alarm boxes
Annually
Fire extinguishing systems or suppression systems
Annually
Guard tour equipment
Annually
Interface equipment
Annually
Audible notification appliances
Annually
Textual audible notification appliances (speak
ers) Annually
Visible notification appliances
Annually
Supervising station fire alarm system transmitters
Annually
[1] Test control equipment quarterly when it is not connected to a supervising station.
[2] Replace batteries every five years or sooner if conditions warrant.