King Pigeon Hi-Tech. Co., Ltd. Ver 1.0
GSM/GPRS/3G/4G/Cloud
Network Fault Monitoring Alarm
Command
Return SMS
Setup
PWD+ID+x
x=0~65535,default is 1.
If the device choose Modbus protocol,x=1~255
ID:x
Inquiry
PWD+IDE
24) Setup Communication Protocol
Command
Return SMS
Setup
PWD+ETHON+x
x=0,1,2,3;0 stands for disable,1 stands for Modbus RTU protocol,2 stands
for Modbus TCP protocol,3 stands for MQTT protocol.
Network port:x
Tips:
If choose Modbus RTU protocol, the Server will revert to the setting that domain name is
modbusrtu.kpiiot.com, port is 4000;
If choose Modbus TCP protocol, the Server will revert to the setting that domain name is
mbtcp.my-m2m.com,port is 6655;
If choose MQTT protocol, the Server will revert to the setting that domain name is
mqtt.my-m2m.com,port is 1883;
If want to connect own server,pls setup GPRS communication protocol first,then setup
server parameter.
25) Setup Server Parameter
Command
Return SMS
Setup
Server1:PWD+IP+x+*+y
Server2:PWD+IPB+x+*+y
(x= server IP or domain;y=port,range:0~65535)
1234IPmodbusrtu.kpiiot.com*4000 to setup server1 address
As modbusrtu.kpiiot.com:4000
IP:x
Port:y
Inquiry
Server1:PWD+IP
Server2:PWD+IPB
Delete
Server1:PWD+IPDEL
Server2:PWD+IPBDEL
26) Inquiry Historic Record (Only can inquiry the latest 100 alarm events.)
Command
Return SMS
Example
PWD+HIS+x
(x=1-100,stands
for inquiry qty)
[IMEI Code as Device ID]
Record event 1:
Record event 2:
Record event 3:
( Each SMS will include one IMEI Code as Device ID.)
PWDHIS8 to read the latest 8
historic record.
27) Setup Language
Reset the unit after changing the language. For the reset operation, please refer to "13. Remotely Resett")
Command
Return SMS
Setup
PWD+EN
English