EasyManuals Logo

KNX GIRA Quick Start Guide

KNX GIRA
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Dimming actuator, 4-gang
Switch on the mains voltage of the outputs again. Switch the affected output off and on
again.
When a short-circuit occurs the affected output switches off. Automatic restart when short-
circuit is eliminated within 100 ms (inductive load) or 7 seconds (capacitive or ohmic
load). After that lasting switch-off.
When a short-circuit occurs during the calibration process, the load calibrates itself again
after the short-circuit is eliminated.
Cause 4: load failure.
Check load, replace light bulb. For inductive transformers, check primary fuse and replace
if necessary.
Manual control with button field not possible
Cause 1: Manual control has not been programmed.
Program manual control.
Cause 2: Manual control via bus disabled.
Enable manual control.
None of the outputs can be operated.
Cause 1: All of the outputs are disabled-
Cancel disabling.
Cause 2: Manual mode active.
Deactivate manual mode (switch off continuous manual mode).
Cause 3: Application software missing or faulty.
Check programming and correct.
All outputs off and not possible to switch on
Cause 1: bus voltage failure.
Check bus voltage.
Luminaires flicker or buzz, proper dimming not possible, device buzzes
Cause: wrong dimming principle set
Installation or commissioning error. Disconnect device and luminaire, switch off circuit
breaker.
Check installation and correct.
If the wrong dimming principle has been preselected: Set correct dimming principle.
If dimming actuator calibrates itself incorrectly, e.g. with highly inductive mains or long
load cables: preselect correct dimming principle with commissioning.
LED lamp is dimly lit when dimmer is switched off
Cause: LED lamp is not optimally suited for this dimmer.
Use a compensation module, see accessories.
Use another type of LED lamp or an LED lamp of another manufacturer.
8 Accessories
Compensation module LED Order no. 2375 00
9 Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your re-
sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will
forward the devices to the Gira Service Center.
10 / 11
82402712 10.07.2020

Other manuals for KNX GIRA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KNX GIRA and is the answer not in the manual?

KNX GIRA Specifications

General IconGeneral
Protection ClassIP20
Ambient Temperature-5 °C to +45 °C
Communication ProtocolKNX
MountingDIN Rail
Number of ChannelsDepends on model

Related product manuals