TP-6811 7/16 35Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Voltage Regulator Voltage Regulator V o lts Per
Hertz Slope
% 1-- 10 4
Voltage Regulator Voltage Regulator V o lts Per
Hertz Cut In Frequency
Hz 42 -- 62 59
Voltage Regulator Voltage Regulator Gain 1 -- 255 16
Engine Timing Engine Start Delay s 0 -- 300 0
Engine Timing Engine Cool Down Delay s 300 -- 600 300
Engine Timing Engine Crank On Delay s 10 -- 30 15
Engine Timing Engine Crank Pause Delay s 1--60 15
Engine Timing Engine Number Of Crank Cycles 1--6 3
Genset Protection Genset Low Battery Voltage
Warning Delay
s Read Only 90
Genset Protection Genset High Battery Voltage
Warning Delay
s Read Only 10
Genset Protection Genset Low Battery Voltage
Warning Limit
% 80 -- 100 100
Genset Protection Genset High Battery Voltage
Warning Limit
% 110 -- 135 125
Genset Protection Genset Battery Low Cranking
Voltage Warning Delay
s Read Only 6
Genset Protection Genset Battery Low Cranking
Voltage Warning Limit
% Read Only 60
Engine Protection Engine Locked Rotor Shutdown
Delay
s 3 3
Engine Protection Genset Low Engine Speed
Shutdown Limit
% 75 -- 95 85
Engine Protection Genset High Engine Speed
Shutdown Limit
% No effect. N/A
Engine Protection Engine Low Oil Pressure
Warning Limit
kPa No effect. N/A
Engine Protection Engine High Oil Pressure
Shutdown Limit
kPa No effect. N/A
Generator Protection Loss Of AC Sensing Shutdown
Delay
s Read Only 3
Generator Protection Genset Low Voltage Shutdown
Delay
s Read Only 10
Generator Protection Genset High Voltage Shutdown
Delay
s Read Only 2
Generator Protection Genset Low Voltage Shutdown
Limit
% Read Only 80
Generator Protection Genset High Voltage Shutdown
Limit
% Read Only 120
Generator Protection Genset Short Term Low
Frequency Shutdown Delay
s Read Only 10
Generator Protection Genset Long Term Low
Frequency Shutdown Delay
s Read Only 60
Generator Protection Genset High Frequency
Shutdown Delay
s Read Only 10
Generator Protection Genset Low Frequency
Shutdown Limit
% Read Only 90
Generator Protection Genset High Frequency
Shutdown Limit
% Read Only 110
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.