TP-6811 7/16 37Section 3 Controller
SiteTech Group Notes [
Default Set -
ting
Adjustment
Range *
UnitsParameter
Digital Output B9 Digital Output B9 Value Read Only False Load
Mgmntw
Digital Output B9 Digital Output B9 Event Read Only 65003 Load
Mgmntw
Digital Output B10 Digital Output B10 Value Read Only False Load
Mgmntw
Digital Output B10 Digital Output B10 Event Read Only 65005 Load
Mgmntw
Digital Output B11 Digital Output B11 Value Read Only False Load
Mgmntw
Digital Output B11 Digital Output B11 Event Read Only 65006 Load
Mgmntw
Digital Output B12 Digital Output B12 Value Read Only False Load
Mgmntw
Digital Output B12 Digital Output B12 Event Read Only 65008 Load
Mgmntw
ATS Metering Summary ATS Contactor Position Read Only N/A RXT
ATS Metering Summary ATS Sources Available Read Only N/A RXT
Source 1 Metering Source 1 Rotation Actual Read Only N/A RXT
Source 1 Metering Source 1 Voltage L1-L2 V Read Only N/A RXT
Source 1 Metering Source 1 Voltage L2-L3 V Read Only N/A RXT
Source 1 Metering Source 1 Voltage L3-L1 V Read Only N/A RXT
Source 1 Metering Source 1 Voltage Average Line
To Line
V Read Only N/A RXT
Source 1 Metering Source 1 Frequency Hz Read Only N/A RXT
Source 2 Metering Source 2 Rotation Actual Read Only N/A RXT
Source 2 Metering Source 2 Voltage L1-L2 V Read Only N/A RXT
Source 2 Metering Source 2 Voltage L2-L3 V Read Only N/A RXT
Source 2 Metering Source 2 Voltage L3-L1 V Read Only N/A RXT
Source 2 Metering Source 2 Voltage Average Line
To Line
V Read Only N/A RXT
Source 2 Metering Source 2 Frequency Hz Read Only N/A RXT
ATS Connection
Configuration
ATS Source Read Only N/A RXT
Source 1 System
Configuration
Source 1 System Voltage V 110.0 -- 600.0 Genset
System
Voltage
RXT
Source 1 System
Configuration
Source 1 System Frequency Hz 48.0 -- 62.0 Genset
System
Frequency
RXT
Source 1 System
Configuration
Source 1 Voltage Debounce
Delay
s 1--99 0.5 RXT
Source 1 System
Configuration
Source 1 Low Voltage Pickup % 85 -- 100 90 RXT
Source 1 System
Configuration
Source 1 Low Voltage Dropout % 75 -- 98 90 RXT
Source 1 Calibration Source 1 Calibration Factor
Voltage L1-L2
Read Only 1 RXT
Source 1 Calibration Source 1 Calibration Factor
Voltage L2-L3
Read Only 1 RXT
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.