TP-5594 5/953-14 Scheduled Maintenance
Checking Electrolyte Level
Check the level of electrolyte before each startup.
Remove filler caps and check to see that electrolyte
level is up to bottoms of filler holes. See Figure 3-14.
Refill as necessary with distilled water or clean tap
water. Do not add fresh electrolyte! Be sure filler caps
are tight.
1-046
Figure 3-14. Battery Electrolyte Level
Checking Specific Gravity
Useabatteryhydrometertocheckthespecificgravityof
the electrolyte in each battery cell. While holding the
hydrometer vertical, read the number on the glass bulb
atthetopoftheelectrolytelevel. If the hydrometerused
does not have a correction table, use the one in
Figure 3-15. Determine specific gravity and electrolyte
temperature of battery cells. Locate temperature in
Figure 3-15 and adjust specific gravity by amount
shown. Thebatteryis fullycharged ifthe specificgravity
is 1.260 at an electrolyte temperature of 80°F (26.7°C).
The difference between specific gravities of each cell
should not exceed ±0.01. The battery should be
charged if the specific gravity is below 1.215 at an
electrolyte temperature of 80°F (26.7°C).
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
-- 12.2
-- 6.7
-- 1.1
4.4
10
21.1
26.7
32.2
37.8
43.3
48.9
54.4
60.0
65.6
71.1
15.6
+ .032
+ .030
+ .028
+ .026
+ .024
+ .022
+ .020
+ .018
+ .016
+ .014
+ .012
+ .010
+ .008
+ .006
+ .004
+ .002
0
-- .002
-- .004
--. 006
-- .008
-- .010
-- .012
-- .014
-- .016
-- .018
-- .020
-- .022
-- .024
-- .026
-- .028
°C °F
EXAMPLE NO. 1 --
Temperature below 80°F
(26.7°C)
Hydrometer Reading 1.250
Acid Temperature 20°F
(--6.7°C)
Subtract .024 Sp. Gravity
Corrected Sp. Gravity is
1.226
EXAMPLE NO. 2 --
Temperature above 80°F
(26.7°C)
Hydrometer Reading 1.235
Acid Temperature 100°F
(37.8°C)
Add .008 Sp. Gravity
Corrected Sp. Gravity is 1.243
The Temperature correction amounts to about .004
(4 points) of specific gravity for each 10_F (5.5_C)
change in temperature.
Correction
Figure 3-15. Specific Gravity
Temperature Correction

Table of Contents

Other manuals for Kohler 7CCO

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 7CCO and is the answer not in the manual?

Kohler 7CCO Specifications

General IconGeneral
BrandKohler
Model7CCO
CategoryPortable Generator
LanguageEnglish

Related product manuals