120
Section 7 Decision-Makerr 6000 Controller TP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
No Oil Pressure
Signal
10 NO OIL
PRESSURE
SIGNAL
Fixed 30 4 Not adjustable
Overcrank Shutdown 8, 10 OVER CRANK (lead 12) 0--6 Cycles 3 Cycles
Over Current 10 OVER
CURRENT
RDO-14 Fixed 110% 10 Not adjustable
Over Current Voltage
Restraint Shutdown
(see SD Over
Current Voltage
Restraint)
—
Overfrequency
Shutdown
7, 10 OVER
FREQUENCY
100%--140% 140% Std.
103% FAA
10
Overpower
(see PR Over Power
or SD Over Power)
—
Over Speed
Shutdown
7, 10 OVER SPEED (lead 39) 65--70 Hz (60 Hz)
55--70 Hz (50 Hz)
70 (60 Hz)
70 (50 Hz)
0.25
Overvoltage
Shutdown
7, 8,
10
OVER
VOL TAGE
(lead 26) 105%--135%
of nominal
135%
10-sec time
delay *
2--10
Password
(see Access Code)
—
PGEN
Communication Not
Online
10, 16 PGEN COMM
NOT ONLINE
Not adjustable
PR Loss of Field
(signal)
10, 15 PR LOSS OF
FIELD
10%--100% 20%
5 sec. delay
0--120
PR Over Current
Voltage Restraint
10, 15 PR OVER
CURRENT VR
100%--200% 175%
5 sec. delay
0--120
PR Over Frequency 10, 15 PR OVER
FREQUENCY
100%--140% 102%
5 sec. delay
0--120
PR Over Power 10, 15 PR OVER
POWER
90%--150% 110%
5 sec. delay
0--120
PR Overvoltage 10, 15 PR OVER
VOL TAGE
100%--130% 110%
5 sec. delay
0--120
PR Reverse Power 10, 15 PR REVERSE
POWER
0%--50% 10%
5 sec. delay
0--120
PR Under Frequency 10, 15 PR UNDER
FREQUENCY
80%--100% 96%
5 sec. delay
0--120
PR Under Voltage 10, 15 PR UNDER
VOL TAGE
70%--100% 90%
5 sec. delay
0--120
Remote Shutdown
D15
9, 10 REMOTE
SHUTDWN
Fixed 0 sec.
inhibit,
0 sec. delay
Reverse Power
(see PR Reverse
PowerorSD
Reverse Power)
-
SD Loss of Field
(signal)
10, 15 SD LOSS OF
FIELD
10%--100% 100% 120
sec. delay
0--120
SD Over Current
Voltage Restraint
10, 15 SD OVER
CURRENT VR
100%--200% 200% 120
sec. delay
0--120
SD Over Power 10, 15 SD OVER
POWER
90%--150% 150% 120
sec. delay
0--120
SD Reverse Power 10, 15 SD REVERSE
POWER
0%--50% 50%, 120
sec. delay
0--120
Speed Sensor Fault 10 SPEED
SENSOR
FAULT
Not adjustable
Starter ’A’ 10 STARTER ’A’
FAILURE
Not adjustable
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
] 3x (times) energize time shown in Menu 17