25Section 1 SpecificationsTP-6356 4/12
1.10.3 Settings
Calibration Digital Display Range Setting Default Selection
Voltage Adjustment VOL T ADJ ±20% of System Voltage System Voltage
Controller Gain
REGULATOR GAIN
ADJ
1--10000 100
Underfrequency Unload or
Frequency Setpoint
FREQUENCY
SETPOINT
40 to 70 Hz
1 Hz Below System Frequency (ECM)
2 Hz Below System Frequency
(non-ECM)
Underfrequency Unload Slope SLOPE 0--10% of Rated Voltage (Volts per Cycle) 15 Volts per Cycle at 480 Volts (3.1%)
Reactive Droop VOL TAGE DROOP 0--10% of System Voltage 4% of System Voltage
VAR Control kVAR Adj --50% to 110% 0kVAR
PF Adjust Control PF Adj --0.50 to 1.0 to 0.50 0.8 Lagging
VAR/PF Gain Adjustment VAR/PF Gain Adj 1--10000 100