TP-6356 4/1268 Section 4 Decision-Makerr 340 Controller
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay*
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Status or Fault
Oil Pressure Signal
Loss
5
No Oil Gauge
Signal
User
Defined
30 Not adjustable
Overvoltage
Shutdown
5, 6 Overvoltage RDO—6 105%--135%
115%
2-sec time
delay
2--10
Password
(Access Code)
0(zero)
Starting Aid
Function
4, 5
User
Defined
0--10 sec.
Time Delay Engine
Cooldown (TDEC)
4 RDO—4
00:00--10:00
min:sec
5:00
Time Delay Engine
Start (TDES)
4
User
Defined
00:00--5:00
min:sec
00:01
Underfrequency
Shutdown
5, 6 Underfrequency
User
Defined
80%--95% 90% 10
Undervoltage
Shutdown
5, 6 Undervoltage
User
Defined
70%--95%
85%
10-sec time
delay
5--30
Weak Battery 5 Weak Battery
User
Defined
60% 2
* Inhibited time delay is the time delay period after crank disconnect.