Why is my Komfovent RHP Standard Air Handlers compressor off?
N
Nancy GeorgeSep 7, 2025
Your Komfovent Air Handlers compressor might be off because the heat pump stopped due to insufficient airflow. Try increasing the airflow setting to resolve this.
R
Renee KerrSep 9, 2025
Why is my Komfovent Air Handlers compressor off when the outdoor temperature is between 15°C and 20°C?
R
rmorrisSep 9, 2025
If your Komfovent Air Handlers heat pump is not running when the outdoor temperature is between 15°C and 20°C, it will start automatically as soon as the outdoor temperature changes.
L
Laura SwansonSep 12, 2025
How to troubleshoot VAV calibration fail on Komfovent Air Handlers?
B
bgonzalesSep 12, 2025
If you're experiencing a VAV calibration fail on your Komfovent Air Handlers, check the pressure sensors and their measuring range. The issue may be caused by not connected or faulty pressure sensors. If a sensor needs to be replaced, contact an authorized service representative.
A
Amanda McdonaldSep 12, 2025
What causes low heat exchanger efficiency in Komfovent RHP Standard?
J
Jonathan NguyenSep 12, 2025
Low heat exchanger efficiency in Komfovent Air Handlers can be caused by a few things. It could be due to unfavorable temperature or humidity conditions; in this case, the message will disappear automatically when the air temperature or humidity changes and efficiency increases. It may also be caused by one or two faulty temperature sensors inside the unit. Check the readings of the temperature sensors and contact an authorized service representative if a sensor(s) needs to be replaced. Another potential cause is air mixing between different flows. Check the unit door for tightness and all gaskets or sealant joints for wear.
M
Melissa WrightSep 14, 2025
What does 'Water pump/ coil alarm' mean on Komfovent RHP Standard?
M
Maria CraneSep 14, 2025
The 'Water pump/ coil alarm' on your Komfovent Air Handlers indicates a signal from the water flow sensor or circulation pump has been received. Check if there is enough water in the system and whether the circulation pump and water mixing valves are working.