Questions and Answers

  • M
    Matthew ByrdAug 16, 2025
    How to fix low supply air flow in my Komfovent Fan?
    • B
      Brandy BoyerAug 16, 2025
      If you're experiencing low supply air flow with your Komfovent Fan, here are a few things to check: * Make sure your air filters aren't dirty. If they are, replace them. * Check for any obstructions in your air ducts, dampers, or inlet/exhaust openings. * If you're using VAV air flow control, ensure the pressure sensors are properly connected. If VAV isn't needed, switch to CAV or DCV in the settings. * If the above doesn't resolve the issue, the supply air fan may not be working, and you should contact authorised service.
  • E
    egreenAug 19, 2025
    How to troubleshoot low extract air flow in my Komfovent Fan?
    • J
      joyhernandezSep 12, 2025
      If you're experiencing low extract air flow with your Komfovent Fan, here are a few things to check: * Make sure your air filters aren't dirty. If they are, replace them. * Check for any obstructions in your air ducts, dampers, or inlet/exhaust openings. * If you're using VAV air flow control, ensure the pressure sensors are properly connected. If VAV isn't needed, switch to CAV or DCV in the settings. * If the above doesn't resolve the issue, the extract air fan may not be working, and you should contact authorised service.
  • S
    Shawn TrevinoAug 25, 2025
    Why is the return water temperature low in my Komfovent Fan?
    • J
      John HarrisAug 25, 2025
      If you are experiencing a low return water temperature in your Komfovent Fan, consider the following: * Verify that there is hot water in the water heater system. * Check if the circulation pump is working correctly. * Ensure the water control valve is opening properly. * Confirm that the return water temperature sensor is correctly installed as per the installation manual. If issues persist, contact your installer or authorized service.
  • M
    Monica ThomasAug 27, 2025
    How to fix a heat exchanger failure in my Komfovent Fan?
    • M
      Melissa JonesAug 27, 2025
      If you are experiencing a heat exchanger failure in your Komfovent Fan, here are some things to check: * For DOMEKT R devices, check for any obstructions preventing the rotor heat exchanger from rotating and inspect the rotor belt for tears. * For DOMEKT CF units, if the air bypass damper of the counter-flow heat exchanger is malfunctioning, contact authorised service.
  • M
    Michael WoodAug 30, 2025
    Why is the supply air temperature low in my Komfovent Fan?
    • M
      mburchAug 30, 2025
      If the supply air temperature from your Komfovent Fan is too low, it could be due to: * Integrated heaters not working: Contact authorised service. * Additional heating/cooling devices faulty or incorrectly installed: Contact the company that installed or sold the equipment. * Faulty air temperature sensor: Contact authorised service.
  • N
    Nancy DuffySep 2, 2025
    What causes high supply air temperature in Komfovent Fan?
    • M
      mwangSep 2, 2025
      If the supply air temperature from your Komfovent Fan is too high, it could be due to: * Integrated heaters malfunctioning: Contact authorised service. * Additional heating/cooling devices malfunctioning or incorrectly installed: Contact the company that installed or sold the equipment. * Faulty air temperature sensor: Contact authorised service.
  • A
    Alexander WrightSep 4, 2025
    Why is the heat exchanger icing up in my Komfovent Fan?
    • V
      veronicamaysSep 4, 2025
      If your Komfovent Fan's heat exchanger is icing up, it could be due to: * Malfunctioning antifreeze protection: Check the antifreeze protection settings and ensure any external pre-heater being used is working correctly. * Antifreeze protection switched off: Verify the antifreeze protection settings. If you're not using an integrated or external pre-heater, you can't use a device with a counter-flow heat exchanger when the outside temperature drops below -4 °C.
  • C
    Carlos ReidSep 7, 2025
    What causes low heat exchanger efficiency in Komfovent Fan?
    • W
      Wyatt BurnettSep 7, 2025
      If a message indicates low heat exchanger efficiency in your Komfovent Fan, here are some potential causes and solutions: * If air is being extracted through an additional branch (only for DOMEKT R devices), and that's not needed, close the fifth branch. Ensure any air closing damper in the auxiliary extraction duct is completely closed. * If the supply air volume significantly exceeds the extract air volume and this difference isn't required, unify the air flow settings. * If the unit door isn't fully closed, leading to mixed air flows, ensure the door is firmly pressed shut and that the gaskets aren't worn.
  • E
    edwin78Sep 10, 2025
    What triggers an internal fire alarm in my Komfovent Fan?
    • C
      Chad FergusonSep 10, 2025
      If your Komfovent Fan is showing an internal fire alarm, it may be triggered because: * The internal air temperature is above 50°C: Locate the heat source in the ductwork or unit. * Faulty temperature sensor: Contact authorised service.
  • E
    emilytaylorSep 12, 2025
    What to do, if my Komfovent Fan indicates clogged air filters?
    • J
      Jason WilliamsSep 12, 2025
      If your Komfovent Fan indicates clogged air filters, switch off the device and replace the air filters. After replacement, delete the message.

Summary

Introduction to the Komfovent DOMEKT Unit

Air Handling Unit Functions

Air Flow Control Methods

Details CAV, VAV, and DCV air flow control methods.

Temperature Control Methods

Explains Supply, Extract, Room, and Balance temperature control methods.

Operating Modes Overview

Describes standard, special, ECO, and AUTO operating modes.

AUTO Mode Features

Covers weekly schedules and air quality control within AUTO mode.

Control and Settings

Control Panel C6.1 Interface

Details the C6.1 touch-sensitive display, including screensaver and main screen elements.

C6.1 Panel Operations

Guides on turning on/off, mode changes, parameter overview, and settings.

Mode and Schedule Configuration

Setting air quantity, temperature, air quality, ECO, and weekly schedules.

Main and Advanced Settings

Configuring user interface, network, flow, quality, and control sequence settings.

Troubleshooting

Table of Messages

Lists error codes, possible causes, and user actions for faults.

C6.2 Control Panel Indicators

Explains LED indicators on the C6.2 panel for status and malfunctions.

Periodical Maintenance

Filter Inspection and Replacement

Guidance on checking, replacing, and calibrating air filters.

Device Maintenance Journal

Table for recording performed maintenance and repair works.

Komfovent DOMEKT R 300 V Specifications

General IconGeneral
MountingVertical
Operating temperature-20°C to +40°C
Heat exchanger typeCounterflow
Power supply230 V
Filter classG4