18 Part Number STH063 9/17
Electrical Requirements
Voltage
The maximum allowable voltage variation is ±10% of the
rated voltage on the ice machine model/serial number
plate at start-up (when the electrical load is highest).
Fuse/Circuit Breaker
A separate fuse/circuit breaker must be provided for each
ice machine.
Total Circuit Ampacity
The total circuit ampacity is used to help select the wire
size of the electrical supply.
The wire size (or gauge) is also dependent upon location,
materials used, length of run, etc., so it must be
determined by a qualified electrician.
Refer to ice machine data plate, for electrical
requirements. The ice machine data plate information
overrides all other published data.
n
Warning
All wiring must conform to local, state and national
codes.
n
Warning
The ice machine must be grounded in accordance with
national and local electrical code.