EasyManua.ls Logo

Kozi MX2 - Recommendations for Mobile Home Installation; Mobile Home Combustion Air Intake Requirements; Exhaust Vent Requirements; Other Mobile Home Installation Requirements

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 16
7.2 Recommendations for Mobile Home Installation
1. Make sure there is an effective vapor barrier where the venting penetrates
to the outside of the mobile home. Seal all openings in the vapor barrier
as required.
2. Make sure the mobile home has adequate ventilation. Your stove is a solid
fuel burning appliance. As such, there is a possibility of smoke entering
the room. By making sure the mobile home is adequately vented, you
reduce the chances of smoke remaining in the mobile home.
3. Make sure the venting is properly installed and sealed. Leaking vent
pipes may set off smoke detectors in the mobile home. Also, some fuels
may produce carbon monoxide which, in large amounts, can be fatal.
Make sure the venting is installed properly to prevent leakage of carbon
monoxide into the mobile home.
4. If parts become damaged or need to be replaced, please contact your local
dealer or visit WWW.KOZISTOVES.COM. Do NOT replace parts with
any other parts not specified by your local dealer or manufacturer.
7.3 Mobile Home Combustion Air Intake Requirements
All mobile home installations MUST use combustion air from the outside. This heater
must be connected to the exterior of the mobile home using a noncombustible metal pipe,
with a minimum 2 inch (50 mm) diameter. APR Industries Ltd. part # AK100 (Air Intake
Kit) can be used for this purpose. Use of plastic pipes are not permitted. Please read
the “Combustion Air Intake Requirements” section for more information.
7.4 Exhaust Vent Requirements
Venting a KOZI pellet burner for a mobile home is similar to that of a conventional
home. Please refer to the “Typical Mobile Home Installation Configuration” section for
typical venting configurations the “Venting System” for vent termination and other
requirements. It is highly recommended that 3’. minimum of vertical venting be used (as
shown in Figure 12 and Figure 13). This will reduce the chance of smoke spillage into the
mobile home in case of a power failure.
7.5 Other Mobile Home Installation Requirements
1. The heater must be securely anchored to the floor of the mobile home.
There are 4 holes located on the legs of the stove. Use lag bolts (not
supplied) in these holes to anchor the stove to the floor of the mobile
home.
2. There must be a noncombustible floor protector placed underneath the
heater and extending a minimum of 6” (150 mm) in front of the heater