EasyManua.ls Logo

Kromschroder BCM 400 B2 Series - Technical data; Ambient conditions

Kromschroder BCM 400 B2 Series
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GB-5
D
GB
F
NL
I
E
Check whether the device name/network name
in the network configuration is the same as the
device name saved in the control unit.
1
? The display on the control unit blinks and
indicates
1
.
! An invalid address has been set on theBCM.
! The address check has been activated on the
control unit by setting parameter A080=1.
Check whether the BCM address is in the permit-
ted address range (001toFEF).
Check the value of parameterA080 and adjust
it if necessary.
Adjust the code switch settings on the BCM to
the device name assigned in the network con-
figuration.
2
? The display on the control unit blinks and
indicates
2
.
! The BCM has received an incorrect configuration
from the controller.
Check whether the appropriate GSD/EDS file
has been read into the automation system’s
engineering tool.
Check the device configuration.
3
? The display on the control unit blinks and
indicates
3
.
! The device name for the control unit (BCU) in
the engineering tool is invalid or has not been
entered.
! The address check has been activated on the
control unit by setting parameter A080=1.
Device name on delivery:
e.g. for BCU 460 = not-assigned-bcu-460-xxx
(xxx = address in the range 00 to FEF).
The device name must at least consist of the
expression:
e.g. for BCU 460 = bcu-460-xxx.
Depending on the control unit (BCU) in use,
the default value of the address will change,
see also page 4 (Parameter A080 = 2:
Fieldbus communication without address check).
Delete the expression “not-assigned-” in the
engineering tool or replace it with an individual
name (e.g.Furnacezone-).
Check whether the device name name in the
network configuration is the same as the device
name saved in the control unit.
Check the value of parameterA080 and adjust
it if necessary.
4
? The display on the control unit blinks and
indicates
4
.
! The controller is set to Stop.
Start the controller.
EE
? The display on the control unit blinks and
indicates
E E
.
! Internal communication with bus module has
suffered a fault.
Connected control elements must be equipped
with protective circuits in accordance with the
manufacturer’s instructions.
This prevents high voltage peaks which can
cause malfunctioning of the BCU.
Use interference-suppressed terminal boots
(1kΩ).
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
! Bus module is defective.
Replace the bus module.
For other control unit fault messages, see
BCU46x,480 operating instructions, section
entitled “Assistance in the event of malfunction”.
Technical data
Ambient conditions
Avoid direct sunlight or radiation from red-hot
surfaces on the unit.
Avoid corrosive influences, e.g. salty ambient air
or SO
2
.
The unit may only be stored/installed in enclosed
rooms/buildings.
This unit is not suitable for cleaning with a high-
pressure cleaner and/or cleaning products.
Ambient temperature:
-20 to +70°C (-4 to +158°F),
no condensation permitted.
Transport temperature = ambient temperature.
Storage temperature: -20 to +70°C (-4 to +158°F).
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 65 (for installation in
BCU4xx).
Permitted operating altitude: < 2000 m AMSL.

Related product manuals