BURNER CONTROLS
BCU 465
Technical Information
T-Product 2006 April
Automatic burner control unit with integrated igni-
tion transformer packaged in a single compact
metal housing (IP 54/NEMA 3 rating)
For use with direct spark ignited burners
For continuous operation
For use with modulating or frequency fired control
systems
Includes air valve control
Optional proof of closure switch (POC) control input
Optional digital input for 1,400 °F auto ignition lockout
Displays program status, unit parameters, fault
code or flame signals
Optional optical interface for diagnostic information
and parameter settings
Manual mode for burner adjustments and trouble-
shooting
Select restart or immediate fault lockout in the
event of a flame failure
Removable bottom mounting plate with five (5)
½" conduit openings make installation of electrical
connections simple
Removable terminal blocks to facilitate electrical
field wiring
Meets NFPA 86 standard
CE certified models available

Table of Contents

Questions and Answers

  • H
    Heather WilliamsAug 19, 2025
    What to do if Kromschroder BCU 465 display flashes and indicates 51?
    • N
      Nicole CraigAug 19, 2025
      If the Kromschroder Control Unit display flashes 51, it indicates safety interlocks have discontinuity or there is no voltage at terminal #5. Check the safety interlocks. It can also mean there is a short-circuit at ignition or valve output, so check the wiring and fine-wire fuse F1 (3.15 A, slow-blow, H, to IEC 127-2/5).
  • C
    Christopher SchwartzAug 21, 2025
    What does it mean when Kromschroder BCU 465 Control Unit display flashes and indicates 02 or 03 at start-up?
    • E
      Ernest CamachoAug 21, 2025
      If the Kromschroder Control Unit display flashes and shows 02 or 03 at start-up, even when the flame is verified visually, it could be due to several reasons: * The set value for the switch-off sensitivity is too high. * A short-circuit on the ionization electrode due to soot, dirt, or moisture on the insulator. * The ionization electrode is not correctly positioned at the flame edge. * The gas/air ratio is incorrect. * The flame is not contacting the burner ground because of excessively high gas or air pressure. * The burner or BCU is not adequately grounded. * There is a short-circuit or discontinuity on the flame signal cable. * The UV sensor is soiled. Correct the fault.
  • D
    Danielle JordanAug 23, 2025
    What to do if Kromschroder BCU 465 display flashes and indicates 32?
    • S
      Susan SmithAug 23, 2025
      If the Kromschroder Control Unit display flashes and indicates 32, it means the supply voltage of the unit is below the rated voltage. Ensure the correct voltage supply is used; check the technical data for maximum ratings.
  • P
    porterpeterAug 26, 2025
    What does it mean when Kromschroder BCU 465 display flashes and indicates 0?
    • J
      Jeffrey HillAug 26, 2025
      If the Kromschroder Control Unit display flashes and displays 0, it means the BCU has detected that the Proof of Closure Switch (OCS) input has no proof of closure signal in the standby position. Make sure that the wiring is correct: the BCU needs line voltage when the valve is closed and no voltage signal when the valve is opened. If the wiring is correct, check the switch and the valve for proper operation. If there is any doubt, remove the valve immediately.
  • P
    Pamela LeeAug 28, 2025
    What does it mean when Kromschroder BCU 465 display flashes and displays X?
    • C
      Christine YatesAug 28, 2025
      If the Kromschroder Control Unit display flashes and displays X, it indicates that the BCU has no information that the OCS contact is still open. Ensure the wiring is correct: the BCU needs line voltage when the valve is closed and no voltage signal when the valve is opened during start-up. If the wiring is correct, check the switch and the valve for proper operation. If there is any doubt of correct operation, remove the valve immediately.
  • K
    Kelly RhodesAug 30, 2025
    What does it mean when Kromschroder BCU 465 display flashes and indicates 2 at start-up?
    • M
      Mr. Andrew HoffmanAug 30, 2025
      If the Kromschroder Control Unit display flashes and indicates 2 at start-up, it means the BCU has no information that the OCS contact has opened. Ensure the wiring is correct: the BCU needs line voltage when the valve is closed and no voltage signal when the valve is opened during start-up. If the wiring is correct, check the switch and the valve for proper operation. If you have any doubt of correct operation, remove the valve immediately.
  • A
    Ashley PhelpsSep 1, 2025
    What to do if Kromschroder Control Unit display flashes and indicates 52?
    • D
      davidprinceSep 2, 2025
      If the Kromschroder Control Unit display flashes and indicates 52, it means the BCU is being permanently reset. Apply voltage to terminal 3 only for reset, approximately for 1 second.
  • B
    Breanna KellerSep 4, 2025
    What to do if Kromschroder Control Unit display flashes and indicates 10?
    • K
      Kimberly BlakeSep 4, 2025
      If the Kromschroder Control Unit display flashes and indicates 10, it means the BCU is repeatedly reset (more than 5 times in 15 minutes). Avoid automatic reset by PLC or without monitoring the burner. Reset the BCU manually.
  • J
    Jo WallSep 6, 2025
    What to do if Kromschroder BCU 465 display flashes and indicates 30?
    • J
      Joseph HawkinsSep 6, 2025
      If the Kromschroder Control Unit display flashes and indicates 30, it indicates an abnormal data change in the parameters set for the BCU. Reset the adjustable parameters to their original values using BC-Soft or remove the unit and return it to the manufacturer for inspection.
  • W
    Wendy HansenSep 9, 2025
    What does it mean when Kromschroder Control Unit display flashes and indicates 01?
    • S
      Sharon MayerSep 9, 2025
      If the Kromschroder Control Unit display flashes and displays 01, it could be due to: * The BCU has detected a flame signal simulation without the burner having been ignited (extraneous signal). * The UV tube in the UV sensor UVS is defective and permanently indicates an extraneous signal. Exchange the UV tube, order part # 04065304 – note the operating instructions for the UV sensor. * Flame signal through ceramic insulation.

Summary

Technical Information

Application

Application Examples

Illustrates the BCU 465 in typical modulating and frequency firing control systems.

BCU 465 for Modulating Control Systems

Details the BCU 465's application in modulating control systems.

BCU 465 for Frequency Firing Systems

Explains the BCU 465's application in frequency firing control systems.

Technical Data

Ignition Transformer Ratings and Minimum Cycle Times

Provides data on ignition transformer specifications and cycle times.

System Design Information

Cable Selection and Wiring

Guidelines for selecting and wiring cables for the BCU.

Safety Considerations

Discusses safety periods, interlocks, and low fire delay time.

Operation of Firing Systems at High Temperatures

Explains high-temperature operation and flame management bypass.

Installation Information

Dimensions and Weight

Details physical size and mass of the BCU unit.

Mounting and Installation

Covers mounting methods, enclosure positioning, and fastening.

Fastening Sets

Describes external fastening options for installation.

Terminal Wiring BCU 465

Explains electrical connections via screw terminals.

Operation

Control Interface and Display

Describes the optical interface, labeling, display, and buttons.

Program Status and Fault Indication

Lists display codes for program status and fault conditions.

Normal Start-up Sequence

Details the step-by-step startup process for the BCU 465.

Trial for Ignition and Safety Period

Explains the ignition trial and safety period during startup.

Normal Operation and Flame Monitoring

Describes burner operation and how to view flame signal.

Air Valve Control Functions

Covers purging, air valve operation, pre-purge, and post-purge.

External Air Valve Control

Explains how to externally activate the air valve.

Manual Mode Operation

Details manual mode for adjustments and troubleshooting.

1400°F Auto Ignition Flame Management Bypass

Describes the bypass input for high-temperature operation.

Order Information

Factory Options and Field Programmable Options

Factory Options Overview

Lists configurable factory options like POC and flame failure response time.

Safety Period and Digital Input Configuration

Covers safety period settings and digital input for flame management bypass.

Field Programmable Options

Details options configurable via PC software like switch-off threshold.

Parameter Setting Overview

Guides on how to read and navigate parameters using the BCU.

Parameter Setting Details

Provides a detailed table of parameter settings and their ranges.

Parameter Setting Details - Continued

Continues the detailed table of parameter settings and their values.

Accessories

Troubleshooting

Fault Lockout and Reset Procedures

Explains fault lockout behavior and how to reset the BCU.

Malfunction Assistance and Safety Warnings

Offers guidance for malfunctions and critical safety warnings.

Common Fault Codes and Causes

Addresses common fault codes like 01, c0, cx, c2, and 02.

Further Fault Codes and Safety Checks

Covers fault codes 30, 31, 32, 51, and safety function checks.

Handling Startup and Reset Faults

Addresses fault codes 52, 53, 10, and startup issues.

Contact Information

Kromschroder BCU 465 Specifications

General IconGeneral
ManufacturerKromschroder
TypeBCU 465
CategoryControl Unit
Frequency50/60 Hz
Operating Temperature-20°C to +60°C
Gas TypesNatural gas, LPG
ApprovalsEN 298
Input Voltage24 V DC
Storage Temperature-40°C to +70°C
Relative HumidityMax. 95% non-condensing