23
T-Product · BCU 465 · 2006 April
Factory Options and Field Programmable Options
Flame Proving Period, Param-
eter 23
The flame proving period (delay for
valve 2) is between 0 seconds and
25 seconds.
This time is the delay for high fire
mode. For BCU..O (POC-version),
this means delay for allowing external
air valve control (also see parameter
31); for BCU without POC input this
time is delay for gas valve 2 terminal
#14.
Manual Mode Limit, Parameter
34
If parameter 34 is set =1, the BCU
will return to standby 5 minutes
after the reset/info button was last
pressed. If parameter 34 is set =0,
the BCU will remain in its current
operational state for an unlimited
time.
Automatic Shutdown and Re
-
start after 24 hr Operation, Pa-
rameter 35
If UVS 6 or UVS 8 UV detectors are
used, this function is recommended
to self check the UV detector every
day: parameter 35 = 1: restart, pa-
rameter 35 = 0 continue.
Note: Description of parameters 30,
31, 32 and 36 through 41 see Air
Valve Control of BCU 465
Reading the Parameters
0
Reading the flame signals, factory
options and field programmable op-
tions are explained as follows:
Press the Reset/Information but
-
ton for 2 seconds.
The display changes to param-
eter 01
Release the button.
The display stops at this param-
eter and indicates the related
value.
Press the button again for 2 sec
-
onds.
The display changes to the next
parameter.
All parameters can be recalled
consecutively in this way.
If the button is pressed only
briefly, the display indicates what
parameter is currently being dis
-
played.
The normal program status is
displayed again approx. one
minute after the button was last
pressed or if all parameters are
recalled or if BCU is switched off.