EasyManua.ls Logo

KRUEGER SVE - Preventative Maintenance

KRUEGER SVE
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Form #: SIDOM.4 Page | 17 Revised: 03/19
Figure 9 Reset Cycle for CSC 3011 Control
Preventative Maintenance
1. Inspect pneumatic tubing for loose connections or leaks.
2. Clean out pneumatic line filters regularly according to manufacturer’s recommendations.
Pneumatic Control Troubleshooting
Table 3 Pneumatic Control Troubleshooting
PROBLEM
PROBABLE CAUSE
Controller does not reset to maximum or minimum set point during
balance procedure.
Balancer is using the thermostat for control signal. An artificial
signal must be provided in place of the thermostat.
Controller does not reset to maximum or minimum set point during
operation.
Thermostat is not demanding maximum or minimum air volume.
Main air pressure at the controller is less than 15 psi.
Pneumatic actuator does not stroke fully.
Leak in pneumatic line between the controller and the actuator.
Main air pressure at the controller is less than 15 psi. Leak in the
diaphragm.
Air valve stays in wide open position.
Inlet airflow sensor is blocked by an obstruction (plastic bag, etc.).
Insufficient supply air in the inlet duct.
NOTE: Always check:
Main air pressure (15 psi to 25 psi) at the controller.
● Proper thermostat signal and logic (Direct/Reverse Acting).
● Disconnected or kinked pneumatic lines to the controller
● Blocked inlet airflow sensor or insufficient primary supply air.
● Quality of compressed air (oil or water in lines).
● Leaks in the actuator diaphragm.
● Mechanical linkage of the actuator/air valve.

Other manuals for KRUEGER SVE

Related product manuals