Uninterruptible Power Systems
1/2/3KVA
Operation Manual
4256-1749 E

Questions and Answers

  • P
    paynejeanetteAug 3, 2025
    What to do if my KStar UDC9101RTS UPS battery backup time is shorter than expected?
    • J
      Jeremy GouldAug 3, 2025
      If your KStar UPS provides a shorter battery backup time than expected, it could be due to a couple of reasons: 1. The batteries may not be fully charged. Charge the batteries for at least 5 hours and then check capacity. 2. Batteries defect.
  • A
    Alisha DuffyAug 9, 2025
    What to do if KStar UPS shows alarm code 32 and INV or BYPASS led is blinking?
    • C
      Connie JonesAug 9, 2025
      If your KStar UPS displays alarm code 32 and either the INV or BYPASS LED is blinking, it indicates that the UPS is overloaded. To resolve this, remove some of the connected devices from the UPS output to reduce the load.
  • J
    Jay BaxterAug 15, 2025
    What to do if KStar UDC9101RTS UPS shows alarm code 29 and FAULT led is on?
    • Z
      Zachary CummingsAug 15, 2025
      If the KStar UPS shows alarm code 29 and the FAULT LED is lit, it means the UPS shut down automatically due to a short circuit on its output. You should check the output wiring and any connected devices to ensure they are not causing a short circuit.
  • K
    Kelli WardAug 20, 2025
    Why KStar UPS has no indication or alarm when the mains are normal?
    • W
      Wesley LeonardAug 20, 2025
      If your KStar UPS shows no indication or alarm even when the mains are normal, it could be due to these reasons: * The AC input power cord is not properly connected. Check whether the input power cord is firmly connected to the mains. * The AC input is incorrectly connected to the UPS output. Ensure that you plug the AC input power cord into the AC input correctly.
  • A
    aguilarmichaelAug 27, 2025
    What to do if KStar UDC9101RTS shows alarm code 33 and the battery led is blinking?
    • C
      Courtney LewisAug 27, 2025
      If your KStar UPS displays alarm code 33 and the battery LED is blinking, this indicates that the external or internal battery is incorrectly connected. Verify that all batteries are properly connected.

Summary

Important Safety Warning

Maintenance and Fault Safety

Critical safety warnings regarding maintenance, service, and potential hazards like electric shock and battery handling.

Installation and Setup

UPS Setup and Connection

Step-by-step guide for connecting the UPS input and output power, and establishing communication connections.

Operations

UPS Setting Configuration

Guide to configuring UPS settings such as mode, output voltage, and frequency using the control buttons.

Alarm and Fault Code Reference

Reference table for UPS alarm warnings, buzzer sounds, and LED indicators associated with different fault events.

Troubleshooting Guide

Troubleshooting Symptom Table

A table listing common UPS symptoms, their possible causes, and recommended remedies for operational issues.

Storage and Maintenance

Maintenance and Battery Handling

Information on UPS maintenance, battery service life, replacement, and proper disposal procedures.

Technical Specifications

UPS Model Specifications

Detailed specifications for different UPS models (1KVA to 3KVA) including phase, capacity, input/output voltage, and frequency.

KStar UDC9101RTS Specifications

General IconGeneral
CategoryUPS
ModelUDC9101RTS
BrandKStar
Communication InterfaceUSB
Operating Temperature0-40°C
CertificationsCE, RoHS
TypeLine Interactive
Input Voltage230V
Input Frequency50/60 Hz
Output Frequency50/60 Hz
DisplayLCD
Protection FeaturesOverload, short circuit
Relative Humidity0-95% (Non-condensing)