SECTION XII - KPO TROUBLESHOOTING GUIDE
KPO TROUBLESHOOTING TABLE
STARTUP
FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
PHASE
Control displays PH
Audible alarm fails to
clear on start-up
Phase monitor dis-
plays lock-out “Front
Fault
Phase monitor detects
phasing issue or improper
power incoming
Exchange any line voltage wire with the other,
verify incoming power.
LOW VOLTAGE
Control displays PH
Audible alarm fails to
clear on start-up
Phase monitor dis-
plays, lock-out
“Front Fault”
Phase monitor detects volt-
age lower than factory set-
ting.
Verify incoming power. Slowly lower voltage
setting on monitor to match incoming power.
High Voltage
Control displays
“PH”
Audible alarm fails to
clear on startup
Phase monitor dis-
plays lock out “Front
Fault
Phase monitor detects volt-
age higher than factory set-
ting.
Verify incoming power. Slowly raise voltage set-
ting on monitor to match incoming power.
System sounds audible
alarm. Control displays
CP, LP, or HP
A condition exists with the
mechanical system involving
pressure or condensate
flow.
See advanced troubleshooting section below,
or call 1-800-KwiKool.
System starts up but is
not operating in the se-
lected mode.
System is in time out; con-
trol is set above or below
room temperature or control
is adjusted out of operating
parameters.
Wait 3 minutes, review operations guide, Set up
control.