EasyManua.ls Logo

Lambda EMS 7.5-75 - Figure 3.6 A: Remote Programming by External Voltage, Voltage Mode; Figure 3.6 B: Remote Programming by External Voltage,Voltage Mode (as Per 0 - 10 V Option)

Lambda EMS 7.5-75
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAUTION
An opening in the remote programming circuit is effectively a high
programming resistance and will allow an uncontrolled voltage rise
exceeding the maximum output of the power supply. This may cause
possible damage to the power supply and/or load. For this reason, any
programming resistor switcher must have shorting contacts. This type of
shorting switch connects each successive position before disconnecting
the preceding one.
B External DC Voltage:
A variable voltage programs the output from zero to full rated voltage. Configure the
strapping connections on TB1/J1 as shown on Figure 3.6
1. Remove the jumpers between terminals TB1-3, TB1-4 and TB1-5 or J1-3, J1-4 and J1-5.
2. If unit has the 0 to 10 V programming option, connect a link between TB1/J1-5 and
TB1/J1-6 as shown in Figure 3.6b. Otherwise, if the unit has the default 0 to 5 V
programming connect as shown in Figure 3.6a.
3. Connect the programming voltage source between TB1/J1-4 (positive) and TB1/J1-6
(negative).
NOTE: Apply the appropriate programming voltage. Do not apply 0-10V programming
to a unit that has the default (0-5V) programming.
Figure 3.6a: Remote Programming by External Voltage, Voltage Mode
Figure 3.6b: Remote Programming by External Voltage,
Voltage Mode (as per 0 - 10V Option).
C. External DC Current:
A current of 0 to 1mA programs the output from zero to full rated voltage. Configure the
strapping connections on TB1 or J1 as shown on Figure 3.7.
83-473-000 Revision J
3 - 6 Operating Instructions

Table of Contents

Related product manuals