Technical Data
Voltage supply: 230V + 10% - 15% 50/60 Hz
Power input: approx. 34 VA
Ambient temperature:
Operation: + 0°C … +60°C
Transport and storage: -25°C … +60°C
Display: Alphanumeric display, 16-digit switchable to set-point, load rating, status,
actual value feedback, set-point feedback, digital inputs, continuous control
output value, correction input and correction range. Running text display
Admissible ambient humidity: Class F, DIN 40 040
Inputs and outputs: 16 Digital inputs
8-16 Digital outputs
1-5 Analog outputs
12 Analog inputs
all carrying a potential
Digital signal inputs: 16 via floating 24 V DC contact, or optionally via 230 V module,
type 6 60 R 0018
The parasitic capacitance of the 2,2 µF line connected to the digital inputs
must not be exceeded by the FMS self-tests. The line length should be limited
to 100 m.
Load default: Either potentiometer 1-5 kW, current signal (0/4 … 20 mA) or
three-point step control output
Optional: PT 100 direct switching
Feedback inputs: Either potentiometer 1-5 kW, current signal (0/4 … 20 mA)
Optional: Namur transmitter direct switching
Control outputs: 4 or 5 either continuous or three-point step,
on FMS 5 channel 5 fixed continuous
Resolution:
each analog input 999 points, 10 bit
Three-point step:
Recommended running time of
servo drives: 30 s … 60 s
Continuous control output:
Apparent ohmic resistance: 0 … 10 V > 5 kS
0/4 … 20 mA < 600 S
To be used only in a grounded power line network!