FMS Fault Correction Three-point step control output (B)
Aids
B5
nd
Fault 211 221 2 monitoring band fault appears sporadically during operation.
212 222
213 223 Cause:
214 224 Motor is possibly running in wrong direction
215 225 - this may happen on capacitor motors if:
- the capacitor is defective
- there is a broken wire in the motor or in the lead