EasyManuals Logo

Lamtec FMS Series Quick Reference For End User

Lamtec FMS Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
29
3 System Operation
Possible causes:
Relay module not connected or connected wrongly
Relay or relay module defective
External voltage is fed into the corresponding terminal
Terminal 9 and terminal 10 reversed
24V fuse F2 (front panel) defective
Check wiring
Check relay
measure coil for continuity
With relay module V4:
fuse F1-F4, F6 defective
too less load at terminal 82-84
at terminals 82-86 a testing current has to flow in both directions. Otherwise the relay mod-
ule switches all outputs off during the self-test and the FMS gets faulty.
Impedance at a supply voltage of 230V Z<= 100k
110 V Z<= 22k
As the case may be adequate loads have to be connected (e. g. ohmic resistance or RC mod-
ule)
Outputs, which are not switched off by the FMS (e. g. ignition valve at start without pilot burner)
doesn't need any load.
A20
Fault 370
The internal communication is not functioning.
Voltage off and back on
After changing EPROM:
Check whether the monitoring program EPROM is correctly inserted.
Otherwise:
Change processor card
A21
Fault 901, 911, 904,
912, 905, 913, 906,
914, 915
After changing a potentiometer the reference must be inputted again.
Voltage levels are checked in the unit. These can give rise to false errors as a result of incor-
rect external wiring.
Check wiring. In the case of analog inputs the reference element serves for voltage supply to
the potentiometers

Other manuals for Lamtec FMS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec FMS Series and is the answer not in the manual?

Lamtec FMS Series Specifications

General IconGeneral
BrandLamtec
ModelFMS Series
CategoryController
LanguageEnglish

Related product manuals