Appendix Notes on Start without
pre-ventilation
Minimum time for While starting without pre-ventilation there have to be 5 seconds minimum
outside light monitoring idle time betweenthe start of the system ( signal terminal 2) and the
period of the initiation of the ignition (activating the ignition transformer) to give the
flame monitoring device flame monitoring devioce enough time for "outside light monitoring".
Unless otherwise ensured, please extend parameter 755 accordingly.
________________________________________________________________
The flame monitoring device has to get minimum 5 seconds idle time for
outside light monitoring before the ignition will be initiated.
________________________________________________________________
!