Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper
meter- design- level limit limit Standard
No. nation Description values Aids
_____________________________________________________________________________________________________
754 ES aktiv 1 10 100 ES is activated when load 40 P17
falls by X points
755 Verz. ZÜ 1 0 999 Delay time of 0 P19
ignition position relay
756 Verz. GL 1 0 999 Delay time for base load 0 P20
with sep. ignition point
757 Verz. RG 1 0 999 Delay time for control release 0 P21
758 ZEIT NA 1 0 999 Post-ventilation time 0 P18
759 Verz. ZÜ 1 0 30 Ignition delay when setting 0 P29
after actuation of the ignition point
Control unit
768 KuerznLE 1 0 15 Delay time for "Damper open" 5 P72
after fan on
769 D.n.Abs 1 0 1 Leak test 0 P53
0 = Off, 1 = On
772 Dicht Zü 1 0 1 Leak test before starting 1 P53
0 = Off, 1 = On
777 Prgüzeit 1 0 9999 Program monitoring time 4 P40
With content 0 no monitoring occurs
782 VorZüdel 1 2 40 Transformer pre-energise time 3 P51
(pre-ignition time)
783 Stab.zei 1 3 100 Stabilisation time 3 P52
785 ZEIT VO 1 30 999 Pre-ventilation period 30 P54
787 Wartung 1 0 1 Service mode, control unit runs 0 P60
only until stabilisation time
789 Nachbr.z. 1 0 30 Post-combustion time (flame signal 10 P62
irrelevant) in seconds
Power control unit (option)
790 Lasttyp 1 0 2 Load control type 0 P80
0 = off 2 = Atmosphere-controlled unit
1 = Fixed value (possible only where there is
control unit hardware provision for this)
791 Anf.Temp. 0 0 999 Starting maximum temperature 0 P81
792 Anf.Leis 0 0 999 Starting power 0 P82
793 Anf.Zeit 0 0 32767 Starting time in minutes 0 P83
794 ext.Lgre 0 0 1000 External power limit 0 P84
after switching off