6 Commissioning
The O
2
values calculated during burner adjustment are input and stored as follows, regardless
of whether the burner is off or in operation. The O
2
target values can be input arbitrarily. It is
not necessary to observe any particular sequence.
Fig. 6-6 Typical O
2
target value curve
NOTICE
The O
2
target values can only be stored in the programmed firing rate points. If firing rate
points are skipped, the line in between is interpolated.
Switch (1) to target value.
Channel key 4 (4) is used to set the required O
2
target value.
Press the Enter key (3).
NOTICE
Each stored O
2
target value can be changed as many times as necessary, including immedi-
ately after storing it.
Switch (3) to firing rate and
use channel key 1 (5) to call up the next firing rate point;
etc.
As soon as all required O
2
target values have been entered,
switch (2) back to Automatic.
.The O
2
target value curve is now stored.
Turn selector switch (2) to O
2
TRIM
Delete the whole O
2
curve with channel key 4 (4)
upwards.
If only points need to be changed, push channel key 4
(4) downwards.
Turn selector switch (1) to FIRING RATE RATING (firing
rate).
Using channel key 1 (5), the composite curve's pro-
grammed firing rate points can now be called up.