FMS Commissioning Programming Curves
________________________________________________________ AidsAdding points
If a curve has previously been stored that does not contain
twenty points, additional points may be added.
________________________________________________________
Mode selector switch (2) to "Setting”
Selector switch (1) to "Load rating
Run to desired load rating D2
________________________________________________________
If a flashing number appears after the load rating, instead of
adding a new point an old one is overwritten.
________________________________________________________
Selector switch (1) to "Set-point”
Switch (4) up or down
until system is optimally adjusted at the selected load rating D1,C1,E2
On FMS 5: Selector switch (1) to "Channel 5 display”
- set point and actual value feedback are displayed.
Switch (4) (channel 2) up or down
until channel 5 is optimally adjusted
Selector switch (1) to "Actual value feedback”
Wait until feedback has stopped.
Press Acceptance (3)
- Point X (number of the new load rating appears on the display,
if 6 points have previously been entered, "Point 7” appears,
only then is it classified according to its value) A16
if necessary
add further values
otherwise
Store
Note monitoring values A5,A10
________________________________________________________
Up to 20 points can be programmed. A high resolution should
also be used, since this ensures precise firing control.
It is also possible, however, to store fewer than 20 points. This is
advisable, for example when entering an initial, approximate curve.
________________________________________________________
A definitive curve for the FMS should always comprise
at least 10 points.
________________________________________________________